Danfoss EVRA 10 Installation Manual
Danfoss EVRA 10 Installation Manual

Danfoss EVRA 10 Installation Manual

Solenoid valves

Advertisement

Installation Guide

Solenoid valves

EVRA 3–20 and EVRAT 10–20
HCFC, HFC, R717 (Ammonia)
EVRA 3
Nm
kpm
ft-lbs
60
6.0
45.0
Nm
kpm
ft-lbs
20
2.0
15
The manual opener of EVRA/EVRAT 10, 15 and 20 is intended to be activated only during
initial pressure testing of the refrigeration system.
After pressure testing or service-related manual forced opening of the manual opener
the spindle must be turned fully back to back-seated position to avoid any packing
gland leakage.
Furthermore it is essential that the sealing cap is properly reinstalled. This will eliminate
any risk of leakage from the manual opener.
© Danfoss | DCS (MWA) | 2016.11
EVRA 10/EVRAT 10
EVRA 10, 15, 20/EVRAT 10, 15, 20
Nm
kpm
50
5.0
Nm
30
ft-lbs
37
kpm
ft-lbs
3.0
22.5
a.c. ~
a.c. ~
a.c. ~
12 W a.c. ~
20 W d.c. — ---
DKRCI.PI.BN0.K2.00 | 520H7039 | 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EVRA 10 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss EVRA 10

  • Page 1 ~ a.c. ~ a.c. ~ 12 W a.c. ~ 20 W d.c. — --- EVRA 3 EVRA 10/EVRAT 10 EVRA 10, 15, 20/EVRAT 10, 15, 20 ft-lbs 45.0 ft-lbs ft-lbs ft-lbs 22.5 The manual opener of EVRA/EVRAT 10, 15 and 20 is intended to be activated only during initial pressure testing of the refrigeration system.
  • Page 2 EVRA 10 - 20 EVRAT 10 - 20 EVRA 3 EVRA 10 - 20 EVRAT 10 - 20 EVRA 3 © Danfoss | DCS (MWA) | 2016.11 DKRCI.PI.BN0.K2.00 | 520H7039 | 2...

This manual is also suitable for:

Evra 15Evra 3Evrat 10Evrat 15Evrat 20Evra 20

Table of Contents