Before You Begin; Install The Ac Line Filter; Wire The Ac Line Filter - Allen-Bradley Kinetix 5000 Installation Instructions Manual

Ac line filters
Table of Contents

Advertisement

Before You Begin

For general guidelines when laying out your panel and mounting your AC line filter, refer to the
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.
For guidelines specific to your application, refer to your drive-family user manual listed in
Additional Resources on
ATTENTION: To avoid personal injury or damage to equipment due to hazardous voltages,
follow these guidelines when installing your AC line filter. NEC and local regulations always
take precedence:

Install the AC Line Filter

Mount the line filter to the cabinet panel with hardware as specified in the table below.
AC Line Filter
Mounting Bolts
Cat. No.
2198-DB08-F
M5 (#10-32)
2198-DB20-F
2198-DB42-F
M6 (1/4x20)
2198-DB80-F
2198-DB290-F
M10 (3/8x16)
See the System Design for Control of Electrical Noise Reference Manual, publication
GMC-RM001,
for proper high-frequency (HF) bonding techniques to improve overall system
performance.

Wire the AC Line Filter

Wire must be copper with 75 °C (167 °F) minimum rating. Phasing of main AC power is
arbitrary and earth ground connection is required to improve safety and proper operation.
IMPORTANT
page
8.
Disconnect mains power before installation.
Verify that the rated voltage is compatible with the local supply voltage.
Connect the earth ground connection first.
Torque Value
N•m (lb•in)
2.0 (17.7)
4.5 (39.8)
30 (266)
The National Electrical Code and local electrical codes take precedence over the values and
methods provided.
When wiring the line filter for single-phase operation (Kinetix 5500 drives only), do not make
connections to the L3 terminals. Line and load designations must be observed to meet
product specifications.
Rockwell Automation Publication 2198-IN003B-EN-P - March 2015
Kinetix 5000 AC Line Filters 3

Advertisement

Table of Contents
loading

Table of Contents