B6000 User Manual Cimetrics, Inc Introduction The B6030 enables integrating four Modbus TCP or RTU Steam, BTU or Electrical Meters with an existing BACnet Compliant Building Automation System. Using this, you can offer solutions w h i c h sa ve mone y a n d i m p r o v e b u i l d i n g c om fo rt . The B 6 0 3 0 s u p p o r t s t h e following list of meters.
Page 4
B6000 User Manual Cimetrics, Inc • Schneider SquareD ION 62x0 • Schneider SquareD ION 73x0 • Schneider SquareD ION 75x0 • Schneider SquareD ION 7700 • Schneider SquareD ION 83x0/8600 • Schneider SquareD PowerLogic PM710 • Schneider SquareD PowerLogic PM750 •...
Page 5
Foreign Device support to connect to multiple networks and password protected browser based setup screens. The B6030 has a built in web server that allows users to log in using a web browser. Once a user is logged in, configuration is easy and very self explanatory.
Please Note: A user will be able to access the B6030 using the above mentioned IP address at ALL TIMES (even if you have changed the IP address under BACnet/IP settings) Note! We strongly recommend that the power be recycled on the unit at least once every six months...
The Home Page displays four important Objects of each meter that has been configured. The example below shows that this B6030 is connected to four different meters and four important objects from each of those meters. This is not user configurable as it is only a snapshot of the meters configured.
BACnet Device. Default ID is generated from the MAC address of B6030. 6. BBMD IP Address – If you want B6030 to be a foreign device then here you specify IP address of target BBMD. It will enable Foreign Device mode.
B6000 User Manual Cimetrics, Inc Meters Configuration On this screen, a user can configure the four meters that will be integrated into the BACnet/IP network. If the configuration involves a Modbus RTU meter, the user will need to choose the appropriate baud rate and the serial mode.
Page 10
B6000 User Manual Cimetrics, Inc Download configuration : Clicking on this button will initiate a download of the existing configuration. This will be downloaded as a text file. This file can be saved for uploading (without any edits) in the future to restore a previous configuration.
Page 11
B6000 User Manual Cimetrics, Inc Upload Configuration : By Clicking on this button, a user can upload a previously saved configuration file (text). This will restore the configurations in the uploaded file. Restore Default: Clicking on this button will reset the page to factory default.
B6000 User Manual Cimetrics, Inc BACnet Object Status On this screen, a user can view the BACnet Objects of each of the configured Meters. The following parameters of each BACnet Object are viewable Name Object Value Units Status Reliability Description...
B6000 User Manual Cimetrics, Inc Error Log and Statistics This page provides Statistics and Error logs on the configured meters. Reset Configuration Clicking on Restore default will reset the entire device's configuration to factory defaults. Clicking on Discard changes will discard all changes and revert to active configuration.
B6000 User Manual Cimetrics, Inc Activate Configuration Once changes are made to any configuration on the B6030, the changes get saved only after clicking on the "Confirm" button in the Activate Configuration screen. Clicking on this will initiate a reboot of the device and will save the changes that have been made.