Performance Data - 2.5 Ton - York LX SERIES Technical Manual

Split system air conditioners 13 seer – r-410a – 1 phase 1.5 thru 5 nominal tons
Hide thumbs Also See for LX SERIES:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 33
5581709-YTG-A-0818

PERFORMANCE DATA - 2.5 TON

CONDENSER-ONLY DATA (OUTDOOR UNIT)
SATURATED SUCTION
@ COMPRESSOR
MODEL
T (°F)
35
40
YCD30B22S
45
50
55
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15° F subcooling and 15° F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2° F increase in subcooling.
b. Decrease capacity by 1% for each 2° F decrease in subcooling.
3. Maximum recommended condensing temperature is 140° F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
INDOOR COIL MODEL NO.
ID CFM
AIR TEMP.
ENTERING
ID DB (°F)
OUTDOOR UNIT (°F)
ID WB (°F)
55
65
75
85
95
105
115
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 ° F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
58
55 °F
P (PSIG)
MBH
KW
107
26.7
1.67
119
29.5
1.67
130
32.4
1.66
143
35.5
1.67
156
38.8
1.68
YCD30B22S
CF30BXA1
800
80
80
75
57
62
62
T.C.
27.3
28.3
28.1
S.C.
26.2
22.3
19.3
KW
1.62
1.64
1.64
T.C.
27.4
28.0
28.0
S.C.
26.3
22.6
19.6
KW
1.82
1.83
1.83
T.C.
27.5
27.7
27.8
S.C.
26.4
22.9
19.8
KW
2.01
2.03
2.01
T.C.
26.1
26.5
26.7
S.C.
25.0
22.8
19.5
KW
2.28
2.30
2.28
T.C.
24.7
25.4
25.6
S.C.
23.7
22.6
19.2
KW
2.54
2.57
2.56
T.C.
22.9
23.7
23.8
S.C.
22.0
21.7
18.4
KW
2.90
2.92
2.89
T.C.
21.2
22.0
22.0
S.C.
20.4
20.8
17.7
KW
3.26
3.27
3.23
Outdoor Ambient Temperature
65 °F
75 °F
MBH
KW
MBH
KW
MBH
25.4
1.86
24.0
2.06
22.7
28.0
1.86
26.5
2.06
25.1
30.7
1.85
29.2
2.06
27.6
33.7
1.86
32.0
2.06
30.3
36.8
1.87
34.9
2.07
33.1
1000
80
80
80
80
67
72
57
62
29.4
29.7
27.9
28.8
28.5
18.3
14.5
26.7
23.3
20.2
1.65
1.66
1.63
1.64
1.64
29.4
30.3
28.0
28.5
28.4
18.7
15.0
26.9
23.9
20.7
1.84
1.85
1.83
1.84
1.83
29.5
30.9
28.2
28.3
28.3
19.1
15.4
27.1
24.5
21.2
2.04
2.04
2.02
2.04
2.02
28.8
30.6
27.2
27.3
27.3
19.1
15.4
26.1
24.4
21.1
2.32
2.32
2.29
2.31
2.29
28.0
30.3
26.1
26.3
26.3
19.1
15.3
25.0
24.3
21.1
2.59
2.61
2.55
2.58
2.56
26.4
28.9
24.5
24.7
24.4
18.5
14.9
23.5
23.2
20.3
2.94
2.97
2.91
2.92
2.90
24.7
27.5
22.9
23.1
22.6
17.9
14.4
22.0
22.0
19.6
3.28
3.34
3.27
3.27
3.24
85 °F
95 °F
KW
MBH
KW
MBH
2.29
21.3
2.55
19.7
2.28
23.6
2.53
21.9
2.27
26.0
2.52
24.3
2.28
28.6
2.52
26.8
2.29
31.3
2.52
29.4
75
80
80
80
80
62
67
72
57
62
29.8
30.1
28.4
29.2
19.0
15.2
27.2
24.4
1.65
1.67
1.63
1.65
29.9
30.7
28.6
29.1
19.5
15.7
27.5
25.3
1.85
1.86
1.83
1.85
30.0
31.3
28.9
29.0
20.0
16.2
27.7
26.1
2.05
2.06
2.03
2.05
29.3
31.1
28.2
28.1
20.3
16.2
27.1
26.1
2.33
2.34
2.30
2.31
28.6
30.8
27.5
27.2
20.6
16.3
26.4
26.1
2.60
2.62
2.57
2.58
27.0
29.4
26.1
25.7
20.2
15.9
25.0
24.7
2.95
2.99
2.93
2.93
25.3
28.0
24.6
24.3
19.8
15.6
23.6
23.3
3.30
3.36
3.28
3.28
Johnson Controls Unitary Products
105 °F
115 °F
KW
MBH
KW
2.86
18.1
3.22
2.84
20.2
3.20
2.82
22.4
3.17
2.81
24.8
3.15
2.81
27.3
3.14
1200
75
80
80
62
67
72
28.9
30.2
30.6
21.0
19.6
15.8
1.64
1.66
1.68
28.9
30.3
31.2
21.8
20.3
16.4
1.84
1.86
1.88
28.8
30.5
31.8
22.5
20.9
16.9
2.04
2.06
2.07
27.9
29.8
31.6
22.7
21.5
17.0
2.30
2.34
2.35
27.0
29.2
31.3
23.0
22.1
17.2
2.56
2.61
2.63
25.0
27.6
29.9
22.2
21.9
17.0
2.91
2.96
3.00
23.1
25.9
28.5
21.5
21.7
16.8
3.25
3.31
3.37