Figure D1: Wiring To Hach Series 5000 Analyzer, Models 60000 - 60004 - Sentry SPD 5.5.5 Installation And Operation Manual

Sentrysafe recording equipment user manual
Table of Contents

Advertisement

Sample Sequencer
NOTES:
1)
Program Hach analyzer to
output 4-20 mA by selecting
appropriate DIP switch on the
Hach Microprocessor board in the
Hach control unit. Consult Hach
manual.
2)
Program Hach analyzer to
output system alarm on Relay 3.
3)
Program Hach analyzer to
output
end-of-measurement
signal (contact closure) on Relay
4.
4)
If remote track & hold option
is used with Sample Sequencer,
the 4-20 mA REC OUT signal is
also connected in series to the
track & hold boards.
diagram of recorder connections
using remote track & hold output
boards.
5)
If signal switching output
board option is used with Sample
Sequencer, the 4-20 mA REC
OUT signal is also connected in
series to the signal switching
output boards. See diagram of
recorder connections using signal
switching output boards.
FIGURE D1 - Wiring to Hach Series 5000 Analyzer Models 60000 - 60004
SENTRY
Equipment Corp • P. O. Box 127 • Oconomowoc, WI 53066 • 262/567-7256 • FAX: 262/567-4523
See
Web: www.sentry-equip.com • e-mail: sales@sentry-equip.com
Appendix D
68