NOTE
• Air conditioners should not be installed in
areas where corrosive gases, such as
acid or alkaline gas, are produced.
• Do not install the product where it could
be exposed to sea wind (salty wind)
directly. It can result corrosion on the
product. Corrosion, particularly on the
condenser and evaporator fins, could
cause product malfunction or inefficient
performance.
• If outdoor unit is installed close to the
seaside, it should avoid direct exposure
to the sea wind. Otherwise it needs
additional anticorrosion treatment on the
heat exchanger.
Selecting the location(Outdoor unit)
If the outdoor unit is to be installed close to the
seaside, direct exposure to the sea wind
should be avoided. Install the outdoor unit on
the opposite side of the sea wind direction.
Sea wind
Sea wind
INSTALLATION GUIDE AT THE SEASIDE
In case, to install the outdoor unit on the
seaside, set up a windbreak not to be exposed
to the sea wind.
Windbreak
Sea wind
- It should be strong enough like concrete to
prevent the sea wind from the sea.
- The height and width should be more than
150% of the outdoor unit.
- It should be keep more than 70 cm of space
between outdoor unit and the windbreak for
easy air flow.
Select a well-drained place.
• Periodic ( more than once/year )
cleaning of the dust or salt particles
stuck on the heat exchanger by using
water