Greenheck APEX Series Installation, Operation And Maintenance Manual page 21

Energy recovery ventilator
Table of Contents

Advertisement

Modulating Control for Fan Speed
(0-10 VDC)
Parameter
A1-01
Access Level
B1-17
VFD Start-Up Setting
C6-02
Carrier Frequency
D2-02
Ref Lower Limit
E2-01
Motor Rated FLA
H2-01
Terminal MA, MC Function
H3-04
Terminal A1 Bias
L4-01
H2-01 Frequency Detection
L5-01
Auto Restart Attempt
A1-01
Access Level
CO
Sensor Control for Fan Speed
2
(1/2 speed when CO
(Full speed when CO
Multi-Speed Control for Fan Speed
(1/3 or 1/2 speed reduction)
Parameter
A1-01
Access Level
B1-01
Reference Source (Frequency)
B1-17
VFD Start-Up Setting
C6-02
Carrier Frequency
D1-01
Frequency Reference 1
D1-02
Frequency Reference 2
D1-03
Frequency Reference 3
D1-04
Frequency Reference 4
D2-02
Ref Lower Limit
E2-01
Motor Rated FLA
Multi-Function Input Sel 4
H1-04
(Terminal S4)
Multi-Function Input Sel 5
H1-05
(Terminal S5)
Multi-Function Input Sel 6
H1-06
(Terminal S6)
H2-01
Terminal MA, MC Function
H3-10
A2 Not Used
L4-01
H2-01 Frequency Detection
L5-01
Auto Restart Attempt
A1-01
Access Level
®
Setting
V1000
J1000
2
2
1
1
1
1
50%
50%
Motor
Motor
FLA
FLA
5
5
50%
50%
15
15
5
5
0
0
drops below 700 PPM)
2
rises above 800 PPM)
2
Setting
V1000
J1000
2
2
0
0
1
1
1
1
60 Hz
60 Hz
40 Hz
40 Hz
30 Hz
30 Hz
60 Hz
60 Hz
50%
50%
Motor
Motor
FLA
FLA
3
3
4
4
5
NA
5
5
F
NA
15
15
5
5
0
0
CO
Proportional Control
2
Parameter
B1-17
VFD Start-Up Setting
C6-02
Carrier Frequency
D2-02
Ref Lower Limit
E2-01
Motor Rated FLA
Analog Frequency Reference
H3-03
(Gain)
Analog Frequency Reference
H3-04
(Bias)
L2-01
Ride Thru Power Loss
L4-05
Frequency Ref Loss
L5-01
Auto Restart Attempt
A1-01
Access Level
Variable Frequency Drives for
Energy Recovery Wheel
Parameter
A1-01
Access Level
B1-17
VFD Auto Start
C1-04
Decel Time
*C4-01
Torque Gain
C6-02
Carrier Frequency
D2-01
Ref Upper Limit
D2-02
Ref Lower Limit
E2-01
Motor Rated FLA
E2-03
Motor No-Load Current
Multi-Function Input
H1-02
(Terminal S2)
Multi-Function Output
H2-01
(MA, MB, MC)
Multi-Function Input Sel 4
H1-04
(Terminal S4)
Economizer Signal Source
(0-10 VDC)
Analog Frequency Reference
H3-03
(Gain)
Analog Frequency Reference
H3-04
(Bias)
L1-01
Elect Thermal Overload
L2-01
Ride Thru Power Loss
L4-01
Frequency Detection Level
L5-01
Auto Restart Attempt
A1-01
Access Level
* 208/230 volt only
Model APEX Energy Recovery Ventilator
Setting
V1000
J1000
1
1
1
1
50%
50%
FLA
FLA
150%
150%
25%
25%
2
2
0
NA
5
5
0
0
Setting – J1000
2
1
600
0 .6
2
40 or 50*
5%
Motor FLA
Must be less
than FLA
6
4
7
Setting
Honeywell
Carel
Module
Controller
40 or
0
50*
40 or
0
50
2
2
15
5
0
21