Midea Elite Series Technical & Service Manual page 24

Split type, heat pump air conditioners
Table of Contents

Advertisement

Indoor exchanger temp. up
Indoor exchanger temp. down
7.8.5
Auto wind at heating mode
Room temp. up
Room temp. down
7.8.6
Indoor evaporator high-temperature protection at heating mode
Indoor exchanger temp. up
Indoor exchanger temp. down
7.8.7. The louver opens to Standard Angle ANGLHEAT when power is on for the first time
7.9
Defrosting operation (Available for heating only).
Defrosting condition: Defrosting starts when either of the following ①&②:
7.9.1
① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
② Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
7.9.2
Defrosting time
If the temp. difference condition ① is satisfied for less than 40 minutes, this can be regarded as
severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition ② is satisfied for more than 40 minutes, the defrosting time is 6
minutes.
T= Indoor exchanger temp.
T<TE1
TE1<T<TE2
T>TE2
T> TE3
TE3<T<TE4
T<TE4
Condition
T=Indoor Temp.-Setting Temp.
T<2℃
T>2℃
T> 0℃
T<0℃
Condition
T= Indoor exchanger temp.
T<TE8
TE8<T<TE7
T>TE7
T>TE9
T<TE9
Fan speed is high
Fan speed is mid
Fan speed is low
Breeze
Indoor fan speed
Compressor
On
On
Off
Off
On
Temp. of evaporator---room temp.
≤TH
DEFROST
≤TM
DEFROST
≤TL
DEFROST
Meet only if it is Breeze
23
Off
Breeze
Setting fan speed
Setting fan speed
Breeze
Off
High
Med.
Med.
High
Outdoor fan
On
Off
Off
Off
On