The controller provides a BACnet network interface between BACnet client devices and DEOS Controller series devices. It uses the BACnet Master Slave/Token Passing (MS/TP) protocol at the BACnet MAC layer.
RTC 1010 Unit Controller BACnet Communication Module User Guide BACnet Properties Configuration To establish communication on the network, and guarantee a unique ID of devices in a BACnet system, the following properties may have to be configured. Table 1 - BACnet Properties Configuration...
RTC 1010 Unit Controller BACnet Communication Module User Guide Configuration Options The following Configuration options enable you to configure and run the BACnet features of the controllers quickly. Quick Setup Configure the controller for BACnet communication without programming. Ensure that no other device on the network has a MAC address of 0 (the controller's default address).
RTC 1010 Unit Controller BACnet Communication Module User Guide Example 3 MAC=0, Max_Master=1 MAC=2, Max_Master=2 This is an incorrect configuration. The MAC=0 will never find MAC=2 because it will never poll for the master MAC address=2. Example 4 ...
The device instance must be unique system-wide The default value for the device instance=877010 (Vendor_Identifier*1000) Object_Name RTC 1010, programmable up to 32 Bytes Description Programmable up to 32 Bytes (default: RTC 1010 Zoning System) Device Object_Type System_Status Operational...
RTC 1010 Unit Controller BACnet Communication Module User Guide Property Value Writable Programmable (default:0) Represents the MS/TP MAC address in the range of 0 to 254 Proprietary property #1000 Values 128 to 254 represent MS/TP non-token passing slave devices ...
Out_of_Service Property DEOS controllers offer the use of the Out_of_Service writable property. When the value of this property is set to True, it disconnects the object from the physical input, enabling you to input other values. This is useful for special applications or while troubleshooting.
Object Table Information The RTC 1010 system uses the following BACnet object tables, categorized on the basis of their ID. The type is the BACnet Object type, the instance is the BACnet Object. Together, the type and instance form the BACnet Object_Identifier for an object according to the following C-language algorithm: ...
RTC 1010 Unit Controller BACnet Communication Module User Guide Analog Value (AV) Table 6 - Object Table Information: Analog Value (AV) Name Description Notes Present Value AV.1 StaticPressureSetpoint Configuration value that represents the static pressure’s setpoint range. 0”W.C to 5”W.C or 0Pa to 1244Pa COV Increment Resolution 0.01”W.C/2.4Pa...
Page 12
RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes Present Value AV.26 Cfg_SupplyHighLimitRHSetpoint Configuration value of supply high limit humidity setpoint. 40% RH to 95% RH, Resolution 0.5% RH COV Increment Configuration value of high outside air temperature used to determine active humidity setpoint.
Page 13
RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes AV.63 HDem3AVERAGE Average of the 3 highest heating demands. Out_of_Service 0% to 100%, Resolution 0.1% AV.64 HDem4AVERAGE Average of the 4 highest heating demands. Out_of_Service 0% to 100%, Resolution 0.1% AV.65 HDem5AVERAGE...
Page 14
RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes Status value that represents the cooling demand for the Cooling Ramp 2 for stage 1. This value is AV.99 CoolingDemandStage2 Out_of_Service 0% to 100%, Resolution 0.1% based on zone temperature, zone setpoint and values set for the actual ramp.
Page 15
RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes Status value that indicates the rate at which the Baud rate can be configured on an MSTP (0)Auto, 9600, 19200, 38400, and 76800. Resolution AV.165 MSTP_BaudRate Present Value network.
RTC 1010 Unit Controller BACnet Communication Module User Guide Binary Input (BI) Table 7 - Object Table Information: Binary Input (BI) Name Description Notes BI.1 BI1_AuxIn Contact status of the binary input 1: (0) Off, (1) On. Out_of_Service 0 = Off, 1 = On BI.2...
RTC 1010 Unit Controller BACnet Communication Module User Guide Binary Value (BV) Table 9 - Object Table Information: Binary Value (BV) Name Description Notes Configuration of the temperature units used in BACnet. BV.1 Cfg_UnitBACnet If set to (0), the temperature will be in Celsius scale. If set to (1), the temperature will be in...
RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes BV.66 Cfg_AO1Direction Configuration value of analog output 1. (0) Direct Acting, (1) Reverse Acting Present Value 0= Direct Acting 1= Reverse Acting BV.77 Cfg_AI1Direction Configuration value of analog input 1. (0) Direct Acting, (1) Reverse Acting...
RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes Status of the zone mode. RTU mode (1) Auto: Automatic mode changes from heating to cooling based on the zone demand. 1 = Auto MSV.23 SystemMode (2) Heat: Heating mode is activated. The zone will only consider the heating demand.