DEOS RTC 1010 User Manual

Bacnet communication module

Advertisement

Quick Links

RTC 1010
Unit Controller
BACnet Communication Module User Guide
Zoning System
.docx
RTC 1010 -BACnet Guide-170605

Advertisement

Table of Contents
loading

Summary of Contents for DEOS RTC 1010

  • Page 1 RTC 1010 Unit Controller BACnet Communication Module User Guide Zoning System .docx RTC 1010 -BACnet Guide-170605...
  • Page 2: Table Of Contents

    RTC 1010 Unit Controller BACnet Communication Module User Guide Contents Introduction ..................................1 Pre-requisites ................................. 1 Advantages of BACnet ..............................1 BACnet Properties Configuration ........................... 2 Configuration Options ................................ 3 Quick Setup ..................................3 Manual Setup ................................. 3 MAC Address and Max_Master ..........................3 Copy Config ..................................
  • Page 3: Introduction

    The controller provides a BACnet network interface between BACnet client devices and DEOS Controller series devices. It uses the BACnet Master Slave/Token Passing (MS/TP) protocol at the BACnet MAC layer.
  • Page 4: Bacnet Properties Configuration

    RTC 1010 Unit Controller BACnet Communication Module User Guide BACnet Properties Configuration To establish communication on the network, and guarantee a unique ID of devices in a BACnet system, the following properties may have to be configured. Table 1 - BACnet Properties Configuration...
  • Page 5: Configuration Options

    RTC 1010 Unit Controller BACnet Communication Module User Guide Configuration Options The following Configuration options enable you to configure and run the BACnet features of the controllers quickly. Quick Setup Configure the controller for BACnet communication without programming. Ensure that no other device on the network has a MAC address of 0 (the controller's default address).
  • Page 6: Copy Config

    RTC 1010 Unit Controller BACnet Communication Module User Guide Example 3  MAC=0, Max_Master=1  MAC=2, Max_Master=2 This is an incorrect configuration. The MAC=0 will never find MAC=2 because it will never poll for the master MAC address=2. Example 4 ...
  • Page 7: Device Object Properties

     The device instance must be unique system-wide  The default value for the device instance=877010 (Vendor_Identifier*1000) Object_Name RTC 1010, programmable up to 32 Bytes Description Programmable up to 32 Bytes (default: RTC 1010 Zoning System) Device Object_Type System_Status Operational...
  • Page 8: Object Types Supported

    RTC 1010 Unit Controller BACnet Communication Module User Guide Property Value Writable  Programmable (default:0)  Represents the MS/TP MAC address in the range of 0 to 254 Proprietary property #1000  Values 128 to 254 represent MS/TP non-token passing slave devices ...
  • Page 9: Out Of Service Property

    Out_of_Service Property DEOS controllers offer the use of the Out_of_Service writable property. When the value of this property is set to True, it disconnects the object from the physical input, enabling you to input other values. This is useful for special applications or while troubleshooting.
  • Page 10: Object Table Information

    Object Table Information The RTC 1010 system uses the following BACnet object tables, categorized on the basis of their ID. The type is the BACnet Object type, the instance is the BACnet Object. Together, the type and instance form the BACnet Object_Identifier for an object according to the following C-language algorithm: ...
  • Page 11: Analog Value (Av)

    RTC 1010 Unit Controller BACnet Communication Module User Guide Analog Value (AV) Table 6 - Object Table Information: Analog Value (AV) Name Description Notes Present Value AV.1 StaticPressureSetpoint Configuration value that represents the static pressure’s setpoint range. 0”W.C to 5”W.C or 0Pa to 1244Pa COV Increment Resolution 0.01”W.C/2.4Pa...
  • Page 12 RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes Present Value AV.26 Cfg_SupplyHighLimitRHSetpoint Configuration value of supply high limit humidity setpoint. 40% RH to 95% RH, Resolution 0.5% RH COV Increment Configuration value of high outside air temperature used to determine active humidity setpoint.
  • Page 13 RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes AV.63 HDem3AVERAGE Average of the 3 highest heating demands. Out_of_Service 0% to 100%, Resolution 0.1% AV.64 HDem4AVERAGE Average of the 4 highest heating demands. Out_of_Service 0% to 100%, Resolution 0.1% AV.65 HDem5AVERAGE...
  • Page 14 RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes Status value that represents the cooling demand for the Cooling Ramp 2 for stage 1. This value is AV.99 CoolingDemandStage2 Out_of_Service 0% to 100%, Resolution 0.1% based on zone temperature, zone setpoint and values set for the actual ramp.
  • Page 15 RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes Status value that indicates the rate at which the Baud rate can be configured on an MSTP (0)Auto, 9600, 19200, 38400, and 76800. Resolution AV.165 MSTP_BaudRate Present Value network.
  • Page 16: Binary Input (Bi)

    RTC 1010 Unit Controller BACnet Communication Module User Guide Binary Input (BI) Table 7 - Object Table Information: Binary Input (BI) Name Description Notes BI.1 BI1_AuxIn Contact status of the binary input 1: (0) Off, (1) On. Out_of_Service 0 = Off, 1 = On BI.2...
  • Page 17: Binary Value (Bv)

    RTC 1010 Unit Controller BACnet Communication Module User Guide Binary Value (BV) Table 9 - Object Table Information: Binary Value (BV) Name Description Notes Configuration of the temperature units used in BACnet. BV.1 Cfg_UnitBACnet If set to (0), the temperature will be in Celsius scale. If set to (1), the temperature will be in...
  • Page 18: Multi State Value (Msv)

    RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes BV.66 Cfg_AO1Direction Configuration value of analog output 1. (0) Direct Acting, (1) Reverse Acting Present Value 0= Direct Acting 1= Reverse Acting BV.77 Cfg_AI1Direction Configuration value of analog input 1. (0) Direct Acting, (1) Reverse Acting...
  • Page 19: Other

    RTC 1010 Unit Controller BACnet Communication Module User Guide Name Description Notes Status of the zone mode. RTU mode (1) Auto: Automatic mode changes from heating to cooling based on the zone demand. 1 = Auto MSV.23 SystemMode (2) Heat: Heating mode is activated. The zone will only consider the heating demand.
  • Page 20: Notes

    Notes www.deos-controls.com...