Gentex GHSLF Series Manual page 2

Low frequency visible and/or audible signaling appliance

Advertisement

Available languages

Available languages

Table A
Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2016 Edition
Maximum Room Size
Meters
Feet
6.10 x 6.10
20 x 20
8.53 x 8.53
28 x 28
9.14 x 9.14
30 x 30
12.2 x 12.2
40 x 40
13.7 x 13.7
45 x 45
15.2 x 15.2
50 x 50
16.5 x 16.5
54 x 54
16.8 x 16.8
55 x 55
18.3 x 18.3
60 x 60
19.2 x 19.2
63 x 63
20.7 x 20.7
68 x 68
21.3 x 21.3
70 x 70
24.4 x 24.4
80 x 80
27.4 x 27.4
90 x 90
30.5 x 30.5
100 x 100
33.5 x 33.5
110 x 110
36.6 x 36.6
120 x 120
39.6 x 39.6
130 x 130
NA = Not allowable
Candela
Horn Mode
(NORMAL)
Temporal 3 520 Hz
15
Temporal 4 520 Hz
Temporal 3 520 Hz
110
Temporal 4 520 Hz
Temporal 3 520 Hz
177
Temporal 4 520 Hz
N/A =24 VDC nominal operating current data not available
V. WIRING
Wiring for synchronized strobes and horns.
Using this method you may:
Use the Gentex GTSM synchronization protocol to provide synchronization of temporal 3 and temporal 4 tones and mute the horn, if required.
w
NOTICE:
THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE GTSM CONTROL MODULE IS PERMITTED TO
w
SYNCHRONIZE THE HORN.
w THE FOUR PULSE TEMPORAL PATTERN (TEMPORAL 4) CAN ONLY BE OBTAINED ON THIS PRODUCT WHEN USED IN CONJUNCTION WITH THE GENTEX GTSM
SYNCHRONIZATION MODULE OR GTSM SYNCHRONIZATION PROTOCOL.
SEE GTSM CONTROL MODULE MANUAL (550-0632, MANUAL ISSUE DATE (02-01-15) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. GTSM MANUAL CAN BE OBTAINED
w
AT HTTP://WWW.GENTEX.COM/FIRE/PRODUCTS OR CALL GENTEX CORPORATION AT 1-800-436-8391.
Conventional Method:
You may connect the horn directly from a source of rated power without the use of a control module. However, the horns will NOT be synchronized.
GHSLF PRODUCT INFORMATION
Minimum Required Light Output ( Effective Intensity, Cd)
One Light
per Room
15
30
34
60
75
94
110
115
135
150
177
184
240
304
375
455
540
635
GHSLF Horn Decibel Levels and Horn/Strobe Current Ratings
Horn Mode
Temporal 3 520 Hz
Temporal 4 520 Hz
24VDC Nominal Horn/Strobe  
Current Ratings (mA)
24VDC 
24VDC 
Operating 
Operating 
Operating 
Current 
Current 
(LOUD)
(NORMAL)
112.0 mA
144.0 mA
163.0 mA
158.0 mA
175.0 mA
210.0 mA
193.0 mA
223.0 mA
259.0 mA
241.0 mA
291.0 mA
325.0 mA
268.0 mA
293.0 mA
325.0 mA
337.0 mA
391.0 mA
428.0 mA
Four Lights per Room
(One Light per Wall)
NA
NA
NA
15
19
30
30
30
30
37
43
60
60
95
95
135
135
185
Horn Decibel Levels: 
Reverberant Room
Minimum SPL 
Minimum SPL 
at 10Ft. Per ANSI/UL
at 10Ft. Per ANSI/UL
464 (NORMAL)
76.3 dBA
80.6 dBA
1
24VFWR
24VFWR
Regulated 24VDC
Operating 
Max. Operating
Current 
Current 
(LOUD)
(NORMAL)
198.0 mA
269.0 mA
295.0 mA
383.0 mA
329.0 mA
477.0 mA
CAUtION: For the GHLF and GHSLF, only the S+ and S- terminals are to be used for
connection to FACP. The H+ and H- terminals are to be used for dBA selection using
provided jumper. DO NOt APPLY VOLtAGe tO H+ AND H- teRMINALS.
**effective Intensity Requirements for Sleeping Areas
Visible Notification Appliance
Distance from Ceiling to Top of Lens
greater than or equal to 24"
less than 24"
CAUtION: 
Strobe light must be
installed within 16 feet
of the pillow when
used in a sleeping
area.
464 (LOUD)
Temporal 4 520 Hz measured per ANSI/UL 2075
78.8 dBA
1
82.0 dBA
Recommended
2
Horn/Strobe Current Ratings (UL Max)
Over Input Voltage Range of 16-33V (mA)
Regulated 24VDC
Max. Operating 
Current 
Current 
(LOUD)
Current (NORMAL) 
124.0 mA
182.0 mA
195.0 mA
291.0 mA
280.0 mA
326.0 mA
384.0 mA
474.0 mA
365.0 mA
393.0 mA
427.0 mA
525.0 mA
Intensity
110cd
177cd
2
Regulated
Regulated 
24VFWR Max.
24VFWR Max.
Operating 
Operating 
Current (LOUD) 
201.0 mA
252.0 mA
273.0 mA
339.0 mA
348.0 mA
427.0 mA
470.0 mA
555.0 mA
465.0 mA
478.0 mA
639.0 mA
759.0 mA
550-0687
Page 2