EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B
Operation downstream from step controller
Contrac actuators can be driven using step controller pulses instead of an analog setpoint. The following conditions must be fulfilled
in order to implement the step controller pulses:
•
The binary inputs must be configured using the 'STEP CONTROLLER' function.
•
The binary input 1 must be connected with +24 V DC (automatic operation).
•
The 'AUT' operating mode must be selected through the graphic user interface.
+1 -2
Figure 13: Connection example for operation downstream from a step controller
DO 1
Release of
o.k./fault
controller
Controller
+3 -4 +5
-6
7
8
9
Contrac electronic unit
DO 2
DO 3
endpos.
endpos.
0%
100%
0/4 ... 20 mA
Uv
out
10
11 12 13 +14 -15
+26 -27
24V
Setpoint
+ HART
act. pos.
0/4 ... 20 mA
Transmitter
4 ... 20 mA
+28 29
+30 -31
RB
RB
+
-
+
-
Uv
24V
U
M10358
25
I