Gemco Motogard 120 Series Installation Instructions Manual page 5

Over – temperature protection system

Advertisement

Series 135 Motogard
The Series 135 Motogard is designed to take in up
to 3 Thermistors wired in Parallel, and has a Form C
Mechanical Output relay.
Connections
Power Connections:
The 135 Series Motogard relay is designed to operate
off of 120VAC +/-10%, Single Phase, 50/60Hz.
Connect 120VAC to input terminals 1 and 2.
Thermistor Connections:
1. Connect one lead of each Thermistor to terminals
6, 7, and 8 respectively.
2. Connect other leads of each Thermistor to
Common terminal 9.
3. Maximum number of Thermistors in parallel:
Three (3)
4. Note:
If using less than 3 Thermistors.
unused input – Install a 150 Ohm 1/2W resistor
from sensor common (terminal 9) to any unused
input.
Phone: 248-435-0700 Toll Free: 800-635-0289 Fax: 248-435-8120 www.ametekfactoryautomation.com
Output Load Connections:
1. Terminals 3, 4 and 5 comprise a set of "Form C"
contacts with terminal 4 common, Terminal 5 is
the open side and terminal 3 is the closed side.
2. Be sure power is never applied directly across the
contact but always in series with the load.
3. Maximum allowable load – 5 Amps at 120/240VAC
or 28VDC.
4. The closed output of the Motogard Over
temperature
specifically designed to operate directly in series
with most main line contactors. If contact current
is greater than 5 Amps at 115VAC, an interposing
relay must be used.
5. The open output of the Series 135 relay can be
used for trip indication.
Any
Protection
System