TRACO POWER TSP BCMU360 Installation Instructions

Battery controller

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
TSP BCMU360
Mode
Normal
Buffer
*
Observe output current de-rating: 2%/°C (Between +50°C and +60°C for 24V operation or between +40°C and +60°C for 48V operation)
**
Ambient temperature up to +40°C for max. 10 minutes.
***
Ambient temperature up to +40°C for max. 3 minutes.
Parameter
Output Voltage [V]
Output Voltage [V]
Electrical Connections
& Wire Size
Battery Charging Current [A]
Nominal Battery Voltage [V]
Battery Adjustment Range [V]
Battery Resistance Test [mΩ]
Battery Test Current [A]
Battery Test Interval [s]
Battery Warning Voltage [V]
Battery Disconnection Voltage [V]
Thermal Protection
Automatic Battery Temperature
Compensation Range
Battery Remote ON/OFF
Signal Relay Contact Rating
User Settings:
A: Battery Test Period 10 min (not fitted, default); 15 sec (fitted)
B: Output Voltage Settings 48V (not fitted); 24V (fitted, default)
C: Not in use (spare jumper fitted)
Signal Connector:
Temp.Sensor: Connect optional external sensor for automatic end of
charge battery compensation. (Traco Power P/N: TSP-TS)
Battery Remote ON/OFF: Enables remote disconnection of the
battery in buffer mode.
DC OK: Closed contact indicate that the output voltage is higher
than 85-90% of the nominal output voltage.
BAT OK: Closed contact indicates that the battery is charged and
has low resistance. During battery operation, it indicates that the battery
is approaching disconnection point.
DC-IN-OK: Closed contact indicates that at least one of the inputs is present and has voltage within +20 / -3% tolerance.
Remark: Apply torque 0.19Nm for all contacts.
http://www.tracopower.com
Battery Controller
I
Nominal @ 24V
I
out
out
15A
10A*
Condition
Normal Mode
Buffer Mode
Input & Output
Battery Input
Tightening Torque
Normal Mode
25°C Ambient
Normal Mode
Normal Mode
Normal Mode
Normal Mode
Buffer Mode
Buffer Mode
Buffer Mode
Normal Mode
Buffer Mode
Input DC Monitoring
Output Current
Nominal @ 48V
I
Boost @ 24V
out
7.5A
5A*
24V
V
(0.4...0.8)
in-
22.2...22.6
2
2-10 mm
[AWG14-AWG7]
(Max. resistance 20mΩ)
2
4-10 mm
[AWG11-AWG7]
15s (Jumper A fitted: Fig.1 )
-15°C...50°C (external sensor temp. Fig.2)
Switch 5V/5mA (min) to GND (Fig.2)
Figure 1:
J6
Figure 2:
Temp.
Sensor
10
9
I
Boost @ 48V
out
-
15A**
Settings
V
(0.4...0.7)
in-
44.6...45.2
2
1-10 mm
[AWG17-AWG7]
(Max. resistance 40mΩ)
(Max. resistance 10mΩ )
1.76Nm
0.8...1.2
13.6 (Factory Set)
13.0...14.4
100 (max)
2.5A for 60ms (typ)
8..10mins (Jumper A not fitted: Fig.1)
10.4...11.4
9.1...9.7
100°C (at back of chassis)
Level: 0...1.5V
30VDC 1.0A
(Fig.2)
60VDC 0.5A
(Fig.2)
B
A
C
PCB
J6 Link
Ba tte r y
DC OK
Bat OK
Re m o te
O N/O FF
5
8
7
6
4
3
-
7.5A***
48V
Connector
DC-IN
OK
2
1
Rev:0.3 / 0615

Advertisement

loading
Need help?

Need help?

Do you have a question about the TSP BCMU360 and is the answer not in the manual?

Questions and answers

Summary of Contents for TRACO POWER TSP BCMU360

  • Page 1 DC OK Bat OK Re m o te Sensor charge battery compensation. (Traco Power P/N: TSP-TS) O N/O FF Battery Remote ON/OFF: Enables remote disconnection of the battery in buffer mode. DC OK: Closed contact indicate that the output voltage is higher than 85-90% of the nominal output voltage.
  • Page 2 Safety Instructions: Installation Instructions: Before installation read these instructions carefully and com- This equipment is designed for professional indoor pletely. This installation instruction cannot account for every systems. In operation the equipment must not be possible condition of installation, operation or maintenance. accessible.