Page 5
AL101 Steering Gear Alarm System ECR / FWD / AFT / VDR General Specification - Voltage: DC 24V - Current: 1.6A(38A) - Communication: CAN BUS / RS485 / NMEA018(RS422) Features - Compact size, with easy access to wiring on rear connector. - 4 wires CAN BUS data transmission - Software utilizing 20 years experiences in control system - Big square dial keypad for easy access to function button...
Page 6
System Configuration CAUTION! ECR to FWD are the main line RxTx unit, meaning wiring MUST be firstly from ECR to FWD then to either AFT to VDR or vice versa or anyone. If FWD to AFT data line is broken then ECR to FWD will still be operational.
Page 11
Description of AL101-ECR/FWD/AFT/VDR Keypad 1) SILENCE Key This key able to maintain to each lamp’s activation or deactivation After buzzer has activation, this key able to stop to buzzer sound CAUTION! If setting Dip Switch “2” setting done ON, relay output will be working full mode. Meanwhile if setting Dip switch “2”...
3) LAMP TEST Key This key able to all LAMP ON even each lamp has activation or deactivation This key check to LAMP itself working. If on pressing this key both of activation and deactivation lamp ON at once. Then if release this key the deactivation lamp will be OFF 4) DIMMER Key This key able to adjust to LAMP brightness Brightness has total 5 steps.
Page 13
Description of AL101-ECR/FWD/AFT LAMP 1) FU FAIL LAMP Input signal “1” second later LAMP activate 2) PUMP HYDR. LOCK LAMP Input signal “1” second later LAMP activate 3) PHASE FAIL LAMP Input signal “2” second later LAMP activate 4) PUMP LOW OIL LEVEL LAMP Input signal “3”...
Page 22
AL101 Steering Gear Alarm System Chapter 4 Test flow...
Page 23
4.1 Purpose : This alarm testing procedure is to check and confirm that the alarm system is working and meet the design requirement. 4.2 Testing Procedure 4.2.1 Connect the FWD, AFT & ECR panel as single line drawing. 4.2.2 Connect ECR panel to external alarm signals. The alarm signal can be turned off And on by a toggle switch.
Page 24
Step 1: Close PUMP 1 RUN switch Step 2: PUMP 1 RUN indicator light ON Step 3: Buzzer not on. Step 4: Open the PUMP 1 RUN switch Step 5: Indicator light off PUMP 1 STOP Step 1: Close PUMP 1 STOP switch Step 2: PUMP 1 STOP indicator light on Step 3: Buzzer not on.
Page 25
FWD & AFT alarm panel relay Signal output ECR 알람 패널 릴레이 신호 출력 4.7 Testing for signals output to VDR Every indicator light will have a respect +24V DC output at VDR option or data output for NMEA protocol option.
Page 26
1. The Warrantee period, we can guarantee, is one(1) year from your purchasing date 2. Warrantee Exception Clause - Warrantee period is expired. - Any kinds of Mal-function or defection caused by Modification or Repair without Sewhacnm’s permission. - Any kinds of Mal-function, Defection, or External damage, caused by operator - Any kinds of Mal-function, Defection, caused by using spare part from Non-Authorized Distributor or Agent.