Download Print this page

Mitsubishi Electric CMB-WM-V-AA Data Book page 6

Air conditioning systems

Advertisement

1. SPECIFICATIONS
Model name
Number of branch
Power source
Power input
Cooling
(220/230/240) Heating
Current input
Cooling
(220/230/240) Heating
Sound pressure level (measured in anechoice room)
Applicable temperature range of installation site
External finish
Connectable outdoor/heat source unit
Indoor unit capacity connectable to 1 branch
External dimension H x W x D
To outdoor/heat source unit
Refrigerant piping
diameter
High press. Pipe
Low press. Pipe
To Indoor unit
Water piping
Inlet Pipe
diameter
Outlet Pipe
Field drain pipe size
Net weight
Document
Standard
attachment
Accessory
Optional parts
Note
1.Works not included:
Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2.The equipment is for water.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the Sub HBC CONTROLLER at least 5 m away from any indoor units.)
4.Please install the Sub HBC controller in a place where noise will not be an issue.
5.Please attach an expansion vessel (field supply).
6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.
Furthermore, when using copper pipework use a non-oxidative brazing method.
Oxidation of the pipework will reduce the pump life.
7.When brazing the pipes, be sure to braze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.
8.Please install an air purge valve where air will gather in the water circuit.
9.Please refer to the databook or the installation manual for the specified water quality.
10.This unit is not designed for outside installations.
11.Please always make water circulate or pull out the circulation water completely when not using it.
*Please do not use it as a drinking water.
12.Please do not use ground water and well water.
13.When installing the Sub HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.
(Refer to the databook and the installation manual).
14.Can't use singleness. (MAIN HBC CONTROLLER is necessary)
MEES17K102
50 Hz
kW
0.01/0.01/0.01
kW
0.01/0.01/0.01
A
0.05/0.05/0.05
A
0.05/0.05/0.05
dB <A>
°C (D.B.)
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)
mm
in.
mm (in.)
O.D.
mm (in.)
O.D.
mm (in.)
I.D.
mm (in.)
I.D.
mm (in.)
kg (lbs)
CMB-WM1016V-AB
16
1-phase 220-230-240 V
0~32
Galvanized steel plate
Model P80 or smaller
300 x 1,520 x 630
11-13/16 x 59-7/8 x 24-13/16
Connectable outdoor/heat source unit capacity
20 (3/4)
20 (3/4)
O.D. 32 (1-1/4)
53 (117) [62 (137) with water]
Drain Connection pipe (with flexible hose and insulation)
Indoor units
60 Hz
0.01/0.01/0.01
0.01/0.01/0.01
0.05/0.05/0.05
0.05/0.05/0.05
EIo-1
5

Hide quick links:

Advertisement

loading