Page 1
HEATING TECHNIQUE Centrometal d.o.o. - Glavna 12, 40306 Macinec, Croatia, tel: +385 40 372 600, fax: +385 40 372 61 1 Technical instructions for connecting and use of additional equipment Module for control of two heating circuits for boilers PelTec / PelTec-lambda)
Part 1 (installation instructions) PART 1 INSTALLATION INSTRUCTIONS Only authorized persons are permitted for installation of this product Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 3
ADDITIONAL EQUIPMENT (for module CM2K-P) Room corrector „CSK“ Note: On module for control two heating circuits CM2K-P can be connected only room corrector „CSK“ maded by Centrometal d.o.o. factory. On CM2K-P can be connected two room correctors „CSK“, one per each heating circuit.
Page 4
Connecting 1.0 CONNECTING CM2K MODUL TO THE BOILER Connecting CM2K module with boiler PelTec / PelTec-lambda is done by using UTP cable. CM2K PelTec / PelTec-lambda 1 2 3 4 1 2 3 4 Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 5
Connecting the components on CM2K modul 2.0 CONNECTING THE COMPONENTS ON CM2K-P MODUL 1. circuit 2. circuit 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 1 2 3 Main flow Main flow...
Connecting the components on CM2K-P modul PHASES (L) COMMON NEUTRAL (N) COMMON NEUTRAL L L L L L L L N N N N N N N 1 2 3 4 5 6 7 PHASE Connecting the phases for opening or closing mixing valve...
1.Circuit 1.Circuit 1.Circuit Pump is working Mixing valve opens Pump is working Mixing valve closes Mixing valve closes 2.Circuit 2.Circuit 2.Circuit Pump is working Pump is working Mixing valve closes Idle Mixing valve closes Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 8
Date & Time Display File Installation Info Statistic 10. Installation 10.1. Configuration Configuration Ending phase Configuration Begining phase Temperature Stabilization phase Photocell Working phase Cleaning 10.1.1 Configuration Factory: 4.BUF 2. DHC DHC ǀǀ DHW Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 9
When is CM2K regulator turned ON, icon of regulator will appear on the main display. By that icon user will be able to review and change some settings. 05:08 Maintenance Error list Temperature Schedule Operation Date & Time Display File Regulator Installation Info Statistic Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 10
(day / night) 5. Room corrector „CSK“ on 1. circuit (if turned off, icon disappears) Items 1a - 8a have the same meaning as items 1-8 (described above) which only relate to 2. heating circuit. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 11
This parameter defines how many seconds is required for mixing valve opening / closing. THIS NUMBER MUST CORRESPOND EXACTLY TO THE TIME IT TAKES THE ACTUATOR TO OPEN THE VALVE (DEPENDS ON THE TYPE OF ACTUATOR) Technical instructions CM2K-P (PelTec / PelTec-lambda)
- Minimum: 0,1 - Maximum: 4,0 This parameter determine the coefficient of the heating curve. The regulation calculate required flow temperature according to the heating curve and outside temperature to achieve the desired rroom tempearatura Technical instructions CM2K-P (PelTec / PelTec-lambda)
10.17.2. 1. Circuit 1+ Circuit Heating curve Valve time Corrector influance Heating type Min.temp.radiator Corrector Max.temp.radiator Possible selection: - Factory: 1 - Minimum: 0,1 - Maximum: 5,0 This parameter determines coefficient of room corrector influence. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 14
Possible selection: - factory: 20°C - Minimum: 20°C - Maximum: 40°C This parameter determines the minimum possible flow temperature for floor heating. Required flow temperature to satisfy room temperature can not be lower then this parameter. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 15
Night room temp. Max.temp.floor Day/Night Temp. Const. temp. Table 1 Day room temp. Transition Time Possible selection: - factory: 20,0°C - Minimum: 5°C - Maximum: 30,0°C This parameter determines the value of day room temperature. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 16
Possible selection: - factory: Day temperature Day temperature, Night temperature, Table This option enables you to choose type of desired temperature (day, night or table.) In next page you can see how to fill a table. Technical instructions CM2K-P (PelTec / PelTec-lambda)
So, this is time in which will ”flow temperature“ be optimally adjusted to achieve quick transition. In the same way, you can set the same parameters for 2. circuit Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 18
Part 2 (using instructions) PART 2 INSTRUCTIONS FOR USER For any kind of function problems the user is obligated to contact the authorized person who made a first startup. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 19
1+ Circuit Night room temp. Heating curve Day/Night Temp. Table 1 Corrector influance Day room temp. Transition Time Possible selection: - factory: ON -OFF, ON By using this option 1+ circuit can be turned off/on. Technical instructions CM2K-P (PelTec / PelTec-lambda)
This parameter determine the coefficient of the heating curve. The regulation calculate required flow temperature according to the heating curve and outside temperature to achieve the desired rroom tempearatura Coefficient RADIATOR HEATING FLOOR HEATING Outside temperature Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 21
Night room temp. Heating curve Day/Night Temp. Table 1 Corrector influance Day room temp. Transition Time Possible selection: - factory: 20,0°C - Minimum: 5°C - Maximum: 30,0°C This parameter determines the value of day room temperature. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 22
Possible selection: - factory: Day temperature Day temperature, Night temperature, Table This option enables you to choose type of desired temperature (day, night or table.) In next page you can see how to fill a table. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 23
This parameter is time which is presumed that the system will achieve a given room temperature in a transition from day to night mode, and vice versa. So, this is time in which will ”flow temperature“ be optimally adjusted to achieve quick transition. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Setting parameters for 2+ circuit is done in same way like in 1+ circuit. MANUAL TEST 12. Regulator 1. Circuit 2. Circuit Manual test 12.3. Manual test 1. Circuit 2. Circuit User can check the operation of all components of each heating circuit. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 25
Tipka postaje To exit from the manual test has to press the button In the same way you can do manual test for 2+ circuit. 12.3. Manual test 1. Circuit 2. Circuit Technical instructions CM2K-P (PelTec / PelTec-lambda)
floor heating) 5. Room corrector „CSK“ on 1. circuit (if turned off, icon disappears) Items 1a - 8a have the same meaning as items 1-8 (described above) which only relate to 2. heating circuit. Technical instructions CM2K-P (PelTec / PelTec-lambda)
Page 28
Company Centrometal d.o.o. assumes no responsibility for possible inaccuracies in this book originated typographical errors or rewriting, all the pictures and diagrams are principal and it is necessary to adjust each actual situation on the field, in any case the company reserves the right to enter their own products such modifications as considered necessary.