Honeywell PX3 Series Installation Instructions Manual page 4

Heavy duty pressure transducers, 1 bar to 50 bar, 15 psi to 700 psi

Advertisement

Heavy Duty Pressure Transducers
PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi
Diagnostics Mode
The PX3 Series diagnostics mode allows the device to indicate
when internal or external faults occur. If an internal fault occurs,
the output will rail to the preset lower or upper limit values shown
in Figure 3 and Table 6.
External faults will result in the sensor's output exceeding those
preset limits (lower or upper). (For example, if the external sensor
ground (signal) were lost, the sensor output would exceed the up-
per rail of 97.5%.)
Figure 3. Analog Output with Diagnostics
100
90
80
70
60
50
40
30
20
10
0
4
Safety and Productivity Solutions
10
20 30 40 50 60 70 80 90 100
Pressure (psi)
Table 6. Output Transfer Function Codes
Fault Condition
EEPROM Corrupt
Sensor Bridge Open
(any element)
Sensor Bridge Short
(any element)
Low supply voltage
Loss of ground con-
nection
Issue B
32313758
Analog Diagnostic Rail
below lower rail
above upper rail
above upper rail
below lower rail
above upper rail
Upper Rail (97.5%)
Lower Rail (2.5%)