Honeywell PX3 Series Installation Instructions Manual

Heavy duty pressure transducers, 1 bar to 50 bar, 15 psi to 700 psi

Advertisement

Quick Links

Installation Instructions for the
Heavy Duty Pressure Transducers
PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi
General Information
Honeywell's PX3 Series Pressure Transducers use piezoresistive
sensing technology with ASIC (Application Specific Integrated
Circuit) signal conditioning in a brass housing and Metri-Pack
Table 1. Electrical Specifications
Characteristic
Supply voltage:
5 Vdc
3.3 Vdc
Over voltage and reverse voltage
Current consumption:
5 Vdc supply
3.3 Vdc supply
Short circuit protection
Nominal output transfer function:
5 Vdc supply
3.3 Vdc supply
Table 2. Performance Specifications (At 25 °C [77 °F] and under unless otherwise noted.)
Characteristic
Operating temperature range
Storage temperature range
Compensated temperature range
Total Error Band
:
2
-20 °C to 85 °C [-4 °F to 185 °F]
<-20 °C, >85 °C [<-4 °F, >185 °F]
Accuracy BFSL
3
Response time
Turn on time
4
EMC rating
:
5
surge immunity (all leads)
electrostatic discharge
radiated immunity
fast transient burst
immunity to conducted disturbances
radiated emissions
radiated immunity
Insulation resistance
Dielectric strength
Load resistance
Life
Dependent on external and internal seal and cable jacket materials. See Table 5 and Figure 5 for temperature range details.
1
Total Error Band: The maximum deviation from the ideal transfer function over the entire compensated temperature and pressure range. In-
2
cludes all errors due to offset, full scale span, pressure non-linearity, pressure hysteresis, pressure non-repeatability, thermal effect on offset,
thermal effect on span, and thermal hysteresis. See Figure 1.
Accuracy: The maximum deviation in output from a Best Fit Straight Line (BFSL) fitted to the output measured over the pressure range at
3
25 °C [77 °F]. Includes all errors due to pressure non-linearity, pressure hysteresis, and pressure non-repeatability. See Figure 1.
Turn on Time: Duration from power applied until first valid output.
4
Tested using 1,5 m [59.1 in] cable.
5
Safety and Productivity Solutions
Parameter
±0.25 Vdc
±0.25 Vdc
±16 Vdc
3.0 mA max.
1.6 mA to 2.1 mA
yes
0.5 Vdc to 4.5 Vdc (ratiometric to supply)
0.33 Vdc to 2.97 Vdc (ratiometric to supply)
Parameter
-40 °C to 125 °C [-40 °F to 257 °F]
1
-40 °C to 125 °C [-40 °F to 257 °F]
1
-40 °C to 125 °C [-40 °F to 257 °F]
±1.0 %FSS
±2.0 %FSS
±0.25 %FSS
<2 ms (10% to 90% step change in pressure)
<7 ms
±1000 V line to ground per IEC 61000-4-5
±4 kV contact, ±8 kV air per IEC 61000-4-2
10 V/m (80 MHz to 1000 MHz) per IEC 61000-4-3
±1 kV per IEC 61000-4-4
3 V per IEC 61000-4-6
40 dB (30 MHz to 230 MHz), 47 dB (230 MHz to 1000 MHz) per CISPR 11
200 V/m per ISO 11452-2
>100 MOhm, 1500 Vdc
AC1500V, 1 min. or AC1800V, 1 s
>5 kOhm
greater than 10 million full scale pressure cycles over the calibrated pressure range
150 electrical connector. The PX3 Series are fully calibrated and
temperature compensated from -40 °C to 125 °C [-40 °F to
257 °F].
32313758
Issue B

Advertisement

loading

Summary of Contents for Honeywell PX3 Series

  • Page 1 Installation Instructions for the Heavy Duty Pressure Transducers 32313758 Issue B PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi General Information 150 electrical connector. The PX3 Series are fully calibrated and Honeywell’s PX3 Series Pressure Transducers use piezoresistive temperature compensated from -40 °C to 125 °C [-40 °F to...
  • Page 2 Heavy Duty Pressure Transducers Issue B PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi 32313758 Figure 1. TEB Definition and Temperature Performance All Possible Errors Total Error Band Offset Full Scale Span Pressure Non-Linearity Total...
  • Page 3: Product Damage

    (-30 °C to 125 °C [-22 °F to 257 °F]) Honeywell can assist with selecting suitable seal material for the media based on the seal manufacturer’s recommendation. The customer should test the compatibility with the media to ensure that it is correct for the application.
  • Page 4 Heavy Duty Pressure Transducers Issue B PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi 32313758 Diagnostics Mode Table 6. Output Transfer Function Codes The PX3 Series diagnostics mode allows the device to indicate Fault Condition Analog Diagnostic Rail when internal or external faults occur.
  • Page 5 Heavy Duty Pressure Transducers Issue B PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi 32313758 Figure 4. Metri-Pack Mounting Dimensions (For reference only. mm/[in].) Pinout General F1, G1, N1, N2, M1 Pin A = Ground...
  • Page 6 Heavy Duty Pressure Transducers Issue B PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi 32313758 Figure 5. Cable Harness Mounting Dimensions Shown by Pressure Port Type (For reference only. mm/[in].) Wire General F1, G1, N1, N2, M1...
  • Page 7: Personal Injury

    In no event shall Honeywell be liable for consequential, special, or indirect damages. While Honeywell may provide application assistance personally, through our literature and the Honeywell web site, it is buyer’s...