Carrier CRPWREXH030A01 Installation Instructions Manual page 5

Gas heating/electric cooling, electric cooling, and heat pump units 3 to 15 tons small rooftop units vertical power exhaust accessory
Table of Contents

Advertisement

To C11 for Small and Large Cabinet
To IFC-11 for Extra-Large Cabinet
FIELD
BLK
POWER
YEL
SUPPLY
BLU
GRN/YEL
FIELD SUPPLIED
2 X 4 JUNCTION BOX
GROUND
FOR 575V POWER SUPPLY
FOR 208/230V SEPARATE
POWER SUPPLY
Fig. 6 — Power Exhaust Wiring for EconoMi$er IV and EconoMi$er X — 208/230 V and 575 V Units
To C13 for Small
and Large Cabinet
To IFC13 for
Extra-Large Cabinet
BLACK
GRD.
POWER LINE
PLUG
GREEN
3
3
BLACK
1
1
RED
2
2
4
4
OR
3
1
2
4
TO 575V POWER
575V
PRIMARY
SECONDARY
220V
FIELD
SUPPLIED
FUSED
DISCONNECT
GREEN-YELLOW
C2
C1
GRD.
BLACK
EXH.
FAN #1
RELAY
1
3
4
6
BROWN
BROWN
7
9
A
B
TAN
GRAY
TRANSFORMER
NO. HT01AH859
(FIELD-SUPPLIED
AND INSTALLED)
Field Supplied Wiring
575 V transformer No. HT01AH859 is ordered separately from power exhaust
1
Economizer actuator and controller are shipped with the Economizer -
2
not with power exhaust.
Connections from End Switch plug to Economizer controller are
3
made by installer.
If a single power source is to be used, size wire to include
4
power exhaust MCA and MOCP.
For R-410A units, refer to the unit nameplate for MCA and
MOCP for installed power exhaust.
For R-22 units use the following calculations
Check MCA and MOCP when power exhaust is powered
through the unit. Determine the new MCA including the power
exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using an electric cooling, 6-ton R-22 unit with
MCA = 28.9 and MOCP = 35, with CRPWREXJ030A01 power exhaust.
MCA New = 28.9 amps + 1.5 amps = 30.4 amps
If the new MCA does not go over the MOCP published, then MOCP would
not change. The MOCP in this example is 35 amps, the MCA New is below
35, therefore the MOCP is OK. If "MCA NEW" is larger than the published
MOCP, raise the MOCP to the next larger size. For separate power, the
MOCP for the power exhaust will be 15 amps per NEC.
5
POWER
EXHAUST
ACCESSORY
EXH.
FAN #2
TO ECONOMI$ER
2
ECONOMI$ER IV
ACTUATOR
ECONOMI$ER
CONTROLLER
24 VAC
HOT
24 VAC
COM
END
SWITCH
PLUG
TAN
+
1
1
2
2
GRAY
3
3
GRAY
4
4
EF
EF1
3
ECONOMI$ER X
1 2 3 4 5 6 7 8 9 10 11 12
PL-6
TAN
1
2
3
GRAY
4
2