OpenAir™ Electronic Fusible Link
Used with Siemens Fire and Smoke
Damper Actuators
Product Description
The Electronic Fusible Link (EFL) is a heat responsive
device used with the Siemens OpenAir™ UL listed fire
and smoke control damper actuator.
Upon approaching the temperature rating of the EFL
model ordered and installed, the EFL cuts power to the
electronic damper actuator and the actuator's spring
return mechanism closes the damper.
NOTE:
The EFL must be factory-installed. The UL
rating carried by the specific damper and
actuator is assigned as an assembly and
cannot be added in the field.
Replacement EFLs may be field-installed with local
authority approval.
Contents
·
Electronic Fusible Link
·
Two 1.5-inch (38.1 mm) No. 8 pan head self-drilling
screws
Product Numbers
ASK791.165
165°F (74°C)
ASK791.212
212°F (100°C)
ASK791.250
250°F (121°C)
ASK791.350
350°F (177°C)
NOTE:
The EFL is compatible only with OpenAir
GRD, GKD, or GVD
actuators.
Warning/Caution Notations
WARNING:
CAUTION:
Item number A6V11200850, Rev. DA
fire and smoke damper
Personal injury or loss of life may
occur if you do not follow the
procedures as specified.
Equipment damage may occur if
you do not follow the procedures
as specified.
Required Tools
·
1-3/8-inch (35 mm) drill or hole punch
·
No. 2 Phillips bit
Expected Installation Time
15 minutes
Prerequisites
Appropriate OpenAir GJD, GRD, GKD, or GVD series
damper actuator.
Operation
When the EFL detects that its temperature rating is
being approached, the power to the electronic damper
actuator is shut off and the spring mechanism closes the
damper.
NOTE: Depending on the application environment, the
EFL may trip before the listed temperature
rating.
The manual override reset button (see Figure 1) on the
EFL can be pressed when the temperature has cooled
below the EFL setpoint. The EFL device will again be
operational.
GJD,
Installation Instructions
Document No. A6V11200850
Figure 1. Parts Description.
Page 1 of 4
May 1, 2018

Advertisement

loading

Summary of Contents for Siemens OpenAir ASK791.165

  • Page 1 1-3/8-inch (35 mm) drill or hole punch The Electronic Fusible Link (EFL) is a heat responsive · No. 2 Phillips bit device used with the Siemens OpenAir™ UL listed fire and smoke control damper actuator. Expected Installation Time Upon approaching the temperature rating of the EFL...
  • Page 2 Failure to provide a relief hole will keep and/or temperature the EFL requires to the reset button pressed against the duct switch. wall or damper sleeve, and the EFL will fail to operate as intended. Page 2 of 4 Siemens Industry, Inc.
  • Page 3 External Mounting For external mounting, make a 1-3/8-inch (35 mm) diameter hole in the duct wall or damper sleeve. The sensor will protrude into the duct or damper for proper temperature sensing. 3 of 4 Siemens Industry, Inc. Page...
  • Page 4 Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. OpenAir is a trademark of Siemens Schweiz, AG. Other product or company names mentioned herein may be the trademarks of their respective owners.

This manual is also suitable for:

Openair ask791.212Openair ask791.250Openair ask791.350