GAS SF6-Aciditor Manual

Gas analytical equipment

Advertisement

Quick Links

Manual
SF
-Aciditor
6
Version 1.2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SF6-Aciditor and is the answer not in the manual?

Questions and answers

Summary of Contents for GAS SF6-Aciditor

  • Page 1 Manual -Aciditor Version 1.2...
  • Page 2 -Aciditor © G.A.S. Gesellschaft für analytische Sensorsysteme mbH DortmundBioMedicineCenter Otto-Hahn-Straße 15 D-44227 Dortmund, Germany Phone: +49 231 / 97 42 - 65 50 Fax: +49 231 / 97 42 - 65 55 E-Mail: info@gas-dortmund.de Internet: www.gas-dortmund.de 2.2.2010...
  • Page 3: Table Of Contents

    -Aciditor 1 General Information Information about the Manual Explanation of Symbols Scope of Supply Liability and Guarantee Copyright Return and Disposal Customer Service 2 Transport, Packing and Storage Inspection after Transport Transport Packing Storage 3 Cleaning and Maintenance Cleaning Maintenance Exchange of the sensor / Calibration 4 Security Intended Use...
  • Page 4: General Information

    -Aciditor 1 General Information 1.1 Information about the Manual This manual describes a safe and adequate handling of the SF -Aciditor. Following the instructions of the indicated safety aspects and instructions as well as the national and/or local rules and general safety regulations concerning the prevention of accidents are absolutely imperative.
  • Page 5: Scope Of Supply

    -Aciditor 1.3 Scope of Supply Assure that you have received the full scope of supply. If there is any part missing, please contact the G.A.S.-hotline immediately. The scope of supply consists of: • -Aciditor • -Sensor foil sealed • Transport case •...
  • Page 6: Copyright

    Fax: ++49 231 / 97 42 - 65 55 E-Mail: info@gas-dortmund.de The telephone hotline is attainable from Monday to Friday from 8:00 to 17:00 hours. In urgent cases and if you use fax or e-mail, please indicate your telephone number.
  • Page 7: Transport, Packing And Storage

    -Aciditor 2 Transport, Packing and Storage 2.1 Inspection after Transport Check the supply immediately after delivery concerning its completeness and/or transport damages. If you detect outwardly recognizable transport damage, do not receive the supply, or only under reservation. State the extent of the damage on the provided delivery note and/or the transportation documents of the feeder.
  • Page 8: Cleaning And Maintenance

    -Aciditor 3 Cleaning and Maintenance Natural aging and the wear of certain components of the equipment require a regular cleaning and maintenance. 3.1 Cleaning Clean the device only with a dry or easily damp cloth. NOTE! Danger for real values! Do not use cleaning agents, which contain solvents, acids or bases.
  • Page 9: Security

    -Aciditor 4 Security This section gives an overview of all important safety aspects for an optimal protection of the personnel as well as for the safe and trouble free use of the device. Additionally, the individual chapters contain concrete safety references with respect to the prevention of direct dangers which are indicated by symbols.
  • Page 10: Requirements Of The Personnel

    The device is reliable in service when operated according to its intended use. VERY DANGEROUS! Injury or mortal danger! The equipment is not certified for the employment in areas with explosive gas air mixtures (zone 0).
  • Page 11: Introduction

    The methods described above are complicated, expensive, require specially trained personnel and can only be used in a laboratory. Using ion mobility spectrometer (IMS) a good quality assessment of the SF...
  • Page 12: Working Principle

    -Aciditor 5.1 Working Principle The SF -Aciditor is a stand-alone device designed to quickly and accurately measure the amount of sulfur dioxide (SO ) in SF . Because the unit contains an automatic flow and pressure control module, the user does not need to be concerned with setting the correct flow rate, or compensating for variations in equipment pressure.
  • Page 13 -Aciditor While the sensor must be replaced (by the user) every 2 years, its accuracy and sensitivity do not strongly degrade due to use (<2% per month). Calibration is not required. The universally accepted CIGRE B3.02.01 standard for re-usable SF is currently 12 ppm /SOF –...
  • Page 14: System Operation

    -Aciditor 6 System Operation 6.1 Loading of Battery The SF -Aciditor is equipped with a 3.2Ah Lithium-Ion battery which allows to operate the device for more than 10 hours. If the voltage which is always displayed during operation drops under 21V a warning message “Low battery” appears on the display. An automatic shutdown of the SF -Aciditor will be executed if the voltage drops under 18V.
  • Page 15: Insertion Of The So -Sensor

    -Aciditor 6.2 Insertion of the SO -Sensor Before operation of the SF -Aciditor the SO -Sensor that comes in a separate plastic foil has to be insert. How to insert the sensor inside the SF -Aciditor is described step by step as follows: 1.
  • Page 16 -Aciditor Note: Carry out the following steps without a gas connection to the hose! 7. Turn on the SF -Aciditor using the “Power”-switch on the front panel of the device and wait until the main screen is displayed (see picture). Pressing “Settings”...
  • Page 17: Operation Of The Sf -Aciditor

    -filled compartment. Information! The SF -Aciditor has no internal valve. If there is an open connection to an -filled compartment, the gas passes through the device with 20 L/h. This, independently whether the device is turned on or off !!
  • Page 18 6.4. 8. Disconnect the SF -Aciditor from the SF -filled compartment. 9. Disconnect the connected sampling bag or recycling system from the “Gas Outlet” on the back of the SF -Aciditor (optional). Information! Using a recycling system or sampling bag closely watch the filling status...
  • Page 19: Purging Of The Sf

    Therefore keep SF -Aciditor turned on, disconnect the hose at the gas inlet and press “Flush” on the touchpad display. The pump starts pumping ambient air through the sensor (see picture). Air has to be pumped through the sensor until the SO concentration has again reached 0 .
  • Page 20: Settings

    -Aciditor 6.5 Settings For adjusting the settings of the SF -Aciditor press “Settings” on the touchpad display. The following screen appears. 6.5.1 Turn on/off beeper In the first menu point the beeper for all acoustic signals like keypad tones, alarm tones, etc. can be turned on and off.
  • Page 21 -Aciditor Information! Using the SO -sensor for more than two years leads to an incorrect reading of the sensor. (<2% per month of signal degradation) Pressing the left arrow on the touchpad switches back to the first menu point of “Settings”. To go back to the main screen press “Back”.
  • Page 22: Exchange Of The So -Sensor

    -Aciditor 6.6 Exchange of the sensor The SO -sensor installed inside the SF -Aciditor has a recommended lifetime of two years to guarantee a correct reading. The lifetime counter on the bottom of the screen reminds the operator when to replace it. The exchange the SO -sensor is described in detail below.
  • Page 23 (red marked). 7. Turn up the partial back panel and fix the marked screws. Note: Carry out the following steps without a gas connection to the hose! 8. Turn on the SF -Aciditor using the “Power”-switch on the front panel of the...
  • Page 24 -Aciditor 11. Confirm the resetting by pressing “YES”. Executing “Back” on the touchpad display switches back to the main screen. The SF Aciditor is now ready for operation again or can be turned off using the power button on the front panel.
  • Page 25: Technical Data

    < 2 % signal degradation per month (linear) Long-term stability < 20 L/h Flow rate approx. 2 minutes Measuring time ⊄ Gas consumption approx. 0.7 L per measurement at ambient pressure Pressure 0.5-35 bar (gaseous) / automatic flow rate regulation Operation Purge function for hose cleaning...