Instructional Leaflet P26841
10250T/E34 Pushbuttons and Indicating Lights Class I
Division 2 Application and Installation Instructions
Ratings
Hazardous Location Class I Division 2 pushbuttons and indicat-
ing lights include both the 10250T and E34 corrosion-resistant
product lines. The 10250T1H (CBFS) factory-sealed contact
blocks have one NO and one NC contact.
®
IND. CONT. EQ.
FOR HAZARDOUS
LOCATIONS.
For use on a flat surface of Type 1, 2, 3, 3S*, 3R, 4, 4X,
12 and 13 enclosures.
* Applies to indicating lights only.
UL Listed and CSA Certified for Class I Division 2
Groups B, C, D, and Class I Zone 2, Group IIB + H2.
WARNING
A LENS MUST BE ATTACHED TO ALL ILLUMINATED
DEVICES
Operator And Adapter Assembly
1.
Assemble adapter to operator or light unit and torque
mounting screws to 7 – 9.5 lb-in (0.8 – 1.07 Nm).
2.
Assemble contact block to adapter and torque mounting
screws to 12 – 16 lb-in (1.36 – 1.81 Nm). Contact block
mounting location "1" is referenced to the panel locat-
ing nib on operator. See illustrations.
®
A162
Effective August 2014
Supersedes July 2014
Contact Ratings ............................................. A600, Q300
Ingress Protection ..................................................... IP65
Temperature Codes per NEC Table 500-5(d) for indicating
lights and illuminated operators having a maximum tempera-
ture over 100°C:
10250T
201H
471H
80H
All selector switches with lamp 120MB
202H
472H
81H
All illuminated devices with lamp 1835
TOUT DISPOSITIF LUMINEUX DOIT COMPORTER UNE
LENTILLE
Locating
Nib
Operator
E34
Temp. code
RB120H
T3C
SB120H
T3C
-
T3C
T3C
RB240H
T3A
SB240H
T3B
-
T3B
T4A
WARNING
2
1
Contact
Blocks
Adapter

Advertisement

loading

Summary of Contents for Eaton 10250T/E34

  • Page 1 Effective August 2014 Instructional Leaflet P26841 Supersedes July 2014 10250T/E34 Pushbuttons and Indicating Lights Class I Division 2 Application and Installation Instructions Ratings Contact Ratings ..........A600, Q300 Ingress Protection ............. IP65 Hazardous Location Class I Division 2 pushbuttons and indicat-...
  • Page 2 Instructional Leaflet P26841 10250T/E34 Pushbuttons And Indicating Lights Effective July 2014 Mounting Panel Spacing And Drilling Drawings Drill mounting hole for vertical or horizontal mount- Terminals for Light Unit ing per the matrix below and diagram to the right. “D” Min.
  • Page 3 10250T/E34 Pushbuttons Instructional Leaflet P26841 And Indicating Lights Effective July 2014 Selector Switch Selection And Assembly — Refer To Mounting Location Of Contact Blocks With Respect To Operator Locating Nib. Contact Block Selection Charts Locating Nib Select intended schematic circuit function. Note in your “cam”...
  • Page 4 Terminal ings. Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com © 1999 Eaton Eaton is a registered trademark. All Rights Reserved Publication No. P26841 / 004 All other trademarks are property August 2014 of their respective owners.