P R O D U C T M A N U A L VA C U U M P U M P S E T - 1 H D S 6 8 0 6 3 2 R E V A

11 Maintenance

Spare part list
Part
Vacuum pump 110/230 V, 50/60 Hz
Expansion tank 1.5 l
Spiral hose 7.5 m
Pressure gauge
Pipe connection 150 mm
Pipe connection 50 mm
Tank connection adapter G3/4"
Tank connection adapter G3/8"
Pipe connection adapter 10S
Hydraulic hose 1 m

12 Troubleshooting

Vacuum can not be generated.
Possible cause
Vacuum pump doesn't work correctly.
Hose or pipe isn't connected correctly.
Spiral or hydraulic hose is leaking.
Ball valve at expansion tank is opened.
Expansion tank is leaking.

13 Disposal

The vacuum pump set consists of materials which may be recycled. The main components are aluminum
and plastics.
However, most of the components are directly in contact with hydraulic oil. Observe the local regulations
for this case. In doubt contact the local ABB representative.

14 Technical data

Parameter
Voltage
Frequency
Minimum pressure
Temperature range (operation)
Temperature range (storage)
Dimensions
Total weight

15 Manufacturer information

ABB AG
High Voltage Products
Brown-Boveri-Strasse 30
63457 Hanau, Germany
For any assistance, support or service we recommend to contact directly our local representatives first.
They have extensive knowledge of the specific customer needs, the individual circumstances and the
possibilities of the whole ABB group and are consequently able to organize an optimal service.
Information
In case of an ABB Power Care contract the customer is able to use our 24-h hotline for free. In case of
emergency our troubleshooting experts offers a fast and reliable support.
24-h hotline: +49 (0) 180 6222 007
Please have the following information ready when calling our 24-h hotline:
• Your contact details
• Designation of station
• Order / Serial No
Number
1HDS112161R0001
1HDS112166R0001
1HDS112167P0001
1HDS112171R0001
1HDS112165R0001
1HDS112165R0002
1HDS112023P0125
9ABA460090P2080
1HDS112177P0001
1HDS112176P0001
Aktion
Check vacuum pump for operation.
Check hose and pipe for correct connection.
Replace the spiral or the hydraulic hose by a new one.
Make sure that ball valve at expansion tank is closed.
Check that expansion tank bottom and top plates are screwed tight together.
Value Unit
110-120 / 220-240 V
50 / 60 Hz
0,01 bar
0...+50 °C
+5...+40 °C
280 x 460 x 580 mm
21 kg
• Bay no
• Module no