Vibration Test; Cleaning; Safety Test - Ebmpapst R3G250-AT39-71 Operating Instructions Manual

Ec centrifugal fan
Table of Contents

Advertisement

R3G250-AT39-71
Faulty connection
Thermal overload
protector responded
Overtemperature of
Insufficient cooling
electronics/motor
Ambient temperature
too high
Unacceptable
operating point
If you have any other problems, contact ebm-papst.

6.1 Vibration test

Checking the fan for mechanical vibrations based on ISO 14694.
Recommendation: every 6 months. Maximum vibration severity is 3.5
mm/s measured at the motor's fastening diameter on the motor support
plate towards and perpendicular to the motor's axis of rotation.
Fig. 1: Example showing vibration measurement. Positioning of the
sensors will vary depending on the device and the circumstances of
installation.
Item no. 50237-5-9970 · ENG · Revision 90396 · Release 2016-09-21 · Page 10 / 11
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
De-energise, correct

6.2 Cleaning

connection, see
connection diagram.
Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out
Improve cooling. Let
the device cool down.

6.3 Safety test

To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Reduce the ambient
temperature.
Reset by reducing
control input to 0.
Correct the operating
What has to
point. Let the device
be tested?
cool down.
Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact
Check the
device for
damage to
blades and
housing
Mounting the
connection lines
Mounting of
protective earth
connection
Check the
insulation of the
wires for damage
Impeller for
wear/deposits/
corrosion and
damage
Condensate
discharge holes
for clogging, as
necessary
Abnormal
bearing noise
NOTE
Damage to the device during cleaning
Malfunction possible
→ Do not clean the device using a water jet or high-pressure
cleaner.# Do not use any acid, alkali or solvent-
basedcleaning agents.# Do not use any pointed or sharp-
edged objects for cleaning
NOTE
High-voltage test
The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the
high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
How to test?
Frequency
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
acoustic
At least every
6 months
Which
measure?
Repair or
replacement of
the device
Replacement of
the device
Fasten
Fasten
Replace wires
Clean or
replace impeller
Open bore holes
Replace device