zipLink ZL-RFU20 Installation Instructions

6-point fuse module

Advertisement

16-Point Fuse Module
Installation Instructions
1
13
F5
F6
F7
F1
F2
F3
1
Load
COM
Distribution
11
TB1
COM
F6
F5
F7
F1
F2
F3
1
3
TB1
4
6

Specifications

Description*
Operation Voltage
UL Rated Current**
Maximum Current per Circuit
Maximum Current per Module
Number of Circuits
Field to Logic Side Isolation
Insulation Resistance
Surrounding Temperature Range
Approvals
Terminal Block Contacts
Wire Range (Rated Cross Section)**
Wire Strip Length
Screw Torque
Fuses (Not Included)
Replacement Fuse
Dimensions (WxHxD)
Connector Type
Cable/Wire Clearance
Mounting Restrictions
*Connecting cables are for internal wiring only.
**Use Conductors rated 60°/75°C.
***UL rated 0-75VDC applies when using a DC rated fuse (not supplied), example 217 series.
P1
12
Cable Connector
24
F8
F13
F4
F9
F10
10
F5
F6
F7
F8
COM F13
F14
F15
F16
20
F1
F2
F3
F4
COM
F9
F10
F11
F12
TB2
P1 1
12
13
24
F8
F13
F14
F4
F9
TB2
1
10
11
20
7.21" [183.0mm]
16-point fuse connector module
0-250VAC 0-75VDC***
1A per point
2A
32A
16
>10M Ω @ 500VDC
1800VAC applied for 1 second
32 to 140°F (0 to 60°C)
File # E200031 UL, cUL, Class 1, Division 2,
Groups A,B,C,D Hazardous Locations,
CE, EN 61131-2:2007
Copper alloy, tin-lead plated
12-24AWG Solid or Stranded Copper Conductor
(2.5mm²)
0.24-0.27" (6-7mm)
4.4 in-lbs (0.5 Nm)
Sixteen 5x20mm, 250V
See Edison 5x20mm Glass Fuse section range up
to a Max. 2 amp fuse
7.21" x 3.42" x 2.25" (183mm x 86.8mm x 57.2mm)
Molex Micro-Fit 3.0, 24 pin connector, example re-
ceptacle 43020-2400, Pins 43031 Series, Male
0.5" (12.7mm) Required
None
F14
F15
F16
F11
F12
Load
Distribution
TB3
F15
F16
F10
F11
F12
[86.8mm]
3
1
TB3
LOAD
DISTRIBUTION
4
6

Typical Wiring for D2-16TD1-2

Refer to I/O module for power source requirement.
-V
10.2 - 26.4VDC
+V
Typical Wiring when used with
D2-16TD2-2, D2-12TA, D2-12TR.
Refer to I/O module for power source requirement.
ZL RFU20
ZL-RFU20 TB2 Pinouts
Row Pin
Fuse
Terminal
2, 14 --------
1
15
Fuse 5
2
16
Fuse 6
3
17
Fuse 7
4
T
18
Fuse 8
5
O
8, 20 --------
6
P
21
Fuse 13
7
22
Fuse 14
8
23
Fuse 15
9
24
Fuse 16
10
1, 13 --------
11
3
Fuse 1
12
B
4
Fuse 2
13
O
5
Fuse 3
14
T
6
Fuse 4
15
T
7, 19 --------
16
O
9
Fuse 9
17
10
Fuse 10
18
M
11
Fuse 11
19
12
Fuse 12
20
2.30" [58.4mm]
3.42"
2.25" [57.2mm]
1
C
4
5
6
7
C
4
11
TB1
+24 0
1
2
3 NC 0
TB2
Load
Load
1
C
4
5
6
7
C
4
11
TB1
NC 0
1
2
3 NC 0
1
TB2
Load
Load

Fuse Replacement

Remove
Press
and turn
cap CCW.
Install
Push fuse
into holder
Secure
Press
and turn
cap CW.
Terminal Block
Insertion Point
Opening
Dimension
0.098"
[2.5 mm]
0.114"
[2.9 mm]
10
5
6
7
20
TB3
1
2
3
Load
Load
10
5
6
7
20
TB3
2
3
Load
Load

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZL-RFU20 and is the answer not in the manual?

Questions and answers

Summary of Contents for zipLink ZL-RFU20

  • Page 1 ZL RFU20 16-Point Fuse Module Installation Instructions Fuse Replacement ZL-RFU20 TB2 Pinouts Row Pin Fuse Terminal Remove 2, 14 -------- Fuse 5 Fuse 6 Fuse 7 Press Fuse 8 and turn 8, 20 -------- cap CCW. Fuse 13 Install Fuse 14...
  • Page 2 16-Point Fuse Module Installation Instructions DIN Rail Installation Apply ZIPLink Labels and Removal (Supplied with ZIPLink cables) To install ZIPLink module, insert upper tab Find correct label and remove from sheet into DIN rail. Note: For Note: Upper and cable/wire...