Occupancy sensor – wall mounted

Advertisement

Functional Description
If motion is detected by the permanently active PIR sensor, a
radio telegram indicating the occupied status will transmit
immediately. A transmission interval timer starts to run with a
2 minute lockout timer. No radio telegrams will be sent out
until the timer expires.
After the timer has expired, the unit will transmit occupancy
upon a new motion detection. An unoccupied message will be
sent if no motion is detected for period – sending the first 10
minutes, then again at 30 minutes. A heartbeat message can
also be enabled.
Planning:
Take a moment to plan for the sensor's successful operation
and optimal communication with the TILT WLVD. Remove the
sensor form the packaging and place it under a bright light to
provide the required startup charge. Optionally, to ensure the
sensor energy storage is fully charged, insert a CR2032 battery
for 5 minutes while in a well-lit location.
- Ensure the location provides consistent and adequate light
- Install the appropriate lens for the required coverage
- Locate the sensor between 6 and 8 feet (1.8m to 2.4m) high
- For a wide angle coverage, locate the sensor where traffic
moves across the detection pattern, not in and out
- Consider the area's traffic patterns and principal use, for
example, walking, working, lounging, or sleeping.
- Provide a minimum clearance of 4 ft. (1.2m) away from heat
sources, light bulbs, forced air, or ventilation systems
- Consider the construction materials (such as metal) in the
space and obstacles that may interfere with RF signals
Sensor Range
A single occupancy sensor provides sufficient coverage for
most applications. For some applications, multiple sensors
may be required to provide complete coverage.
Coverage Diagrams
Wide Angle Coverage
© Lauren Illumination, 2015
Occupancy Sensor – Wall Mounted Installation Guide
Long Range Coverage
Installing:
(estimated time: 20 minutes)
The mounting plate can be installed flush to the wall or angled
in a corner
NOTE: It is often easier to link the sensor before it is mounted
on the ceiling. Refer to the "Linking" section
Decide where you want to install the occupancy sensor
Remove the mounting plate from the sensor
Decide which of the two installation options is
appropriate
Flush to the Wall:
1. Orient the mounting plate. Using two
pencil marks, mark the two
mounting screw drill points
2. Drill two holes with a 3/16"drill
bit and insert the wall anchors
3. Insert the first screw loosely
and level the mounting plate
4. Insert the second screw then
hand-tighten the first screw
Angled in a corner:
1. Orient the mounting plate.
2. Carefully drill through two of
the four blind holes on the
angled sides of the mounting
plate (one on each side)
3. Mark the two mounting screw
drill points and drill two holes
with the 3/16" drill bit.
4. Insert the wall anchors
5. Insert the two mounting screw
and hand-tighten them.
Fit the sensor into the groove at the bottom of the mounting
plate and close the top.
Page 2