Start-Up , Adjustment, And Safety Check; Start-Up , Adjustment, And Safety Check General; Prime Condensate Trap With Water; Purge Gas Lines - International comfort products R9MSB0601716A Service And Technical Support Manual

R9msb series; single stage, psc blower motor 35" tall, high efficiency condensing gas furnace
Table of Contents

Advertisement

START−UP, ADJUSTMENT, AND SAFETY
CHECK
General
1. Furnace must have a 115-v power supply properly
connected and grounded.
NOTE: Proper polarity must be maintained for 115-v wiring.
Control status indicator light flashes rapidly and furnace
does not operate if polarity is incorrect or if the furnace is not
grounded.
2. Thermostat wire connections at terminals R, W, G,
and Y must be made at 24-v terminal block on
furnace control.
3. Natural gas service pressure must not exceed 0.5
psig (14- in. w.c., 1125 Pa), but must be no less than
0.16 psig (4.5-in. w.c., 350 Pa).
4. Blower door must be in place to complete 115-v elec-
trical circuit and supply power to the furnace
components.
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent
unit operation or performance satisfaction.
These furnaces are equipped with a manual reset limit
switch in burner assembly.
shuts off power to the gas valve if an overheat
condition
(flame
rollout)
assembly/enclosure.
combustion−air supply, improper gas pressure setting,
improper burner or gas orifice positioning, or improper
venting condition before resetting switch.
jumper this switch.
Before operating furnace, check flame rollout manual reset
switch for continuity. If necessary, press button to reset
switch.
EAC-1 (115vac) terminal is energized whenever blower
operates. HUM (24vac) terminal is only energized when the
low pressure switch (LPS) is closed on a call for heat.

Prime Condensate Trap with Water

WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow these warnings could result in personal
injury or death.
Failure to use a properly configured trap or NOT
water-priming trap before operating furnace may allow
positive pressure vent gases to enter the structure
through drain tube. Vent gases contain carbon
monoxide which is tasteless and odorless.
1. Remove upper and middle collector box drain plugs
opposite of the condensate trap. (See Figure 10.)
2. Connect field-supplied 5/8-in. (16 mm) ID tube with at-
tached funnel (see Figure 10) to upper collector box
drain connection.
3. Pour one quart (liter) of water into funnel/tube. Water
should run through collector box, overfill condensate
trap, and flow into open field drain.
4. Remove funnel; replace collector box drain plug.
5. Connect field-supplied 5/8-in. (16 mm) ID tube to
middle collector box drain port.
440 04 6000 00
This switch opens and
occurs
in
the
burner
Correct
inadequate
DO NOT
Specifications subject to change without notice.
6. Pour one quart (liter) of water into funnel/tube. Water
should run through collector box, overfill condensate
trap, and flow into open field drain.
7. Remove funnel and tube from collector box and
replace collector box drain plug.

Purge Gas Lines

If not previously done, purge the lines after all connections
have been made and check for leaks.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber.
Never test for gas leaks with an open flame. Use a
commercially
available
specifically for the detection of leaks to check all
connections. A fire or explosion may result causing
property damage, personal injury or loss of life.

Adjustments

WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting
screw. This can result in unregulated manifold
pressure and result in excess overfire and heat
exchanger failures.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced
furnace life.
DO NOT redrill orifices. Improper drilling (burrs,
out−of−round holes, etc.) can cause excessive burner
noise and misdirection of burner flames. This can
result in flame impingement of heat exchangers,
causing failures. (See Figure 1.)
Figure 1 − Orifice Hole
For proper operation and long term reliability the furnace
input rate must be within +/−2 percent of input rate on
furnace rating plate, or as adjusted for altitude.
soap
solution
made
BURNER
ORIFICE
A93059
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R9msb0801716aR9msb1002122aR9msb1202422a

Table of Contents