Some Parts Of Air Conditioner Does Not Operate - Technibel MCAV180C5VAA Technical Data & Service Manual

Split system air conditioner
Table of Contents

Advertisement

9-3. Some part of air conditioner does not operate.
9-3-1. Only indoor fan does not run.
• Check fan rotation.
Turn fan gently once or twice by
hand.
• Measure resistance of indoor fan
motor winding.
• Check fan motor capacitor.
9-3-2. Only outdoor fan does not run.
• Check fan rotation.
Turn fan gently once or twice by
hand.
• Measure resistance of indoor fan
motor winding.
• Check fan motor capacitor.
(Only for models GR180C7VAA)
• Measure coil resistance of relay.
Fan cannot
be turned.
OK
Fan cannot
be turned.
OK
(1X)
• Check fan casing
foreign matter on
inside.
Fan motor burnout
or foreign matter in
bearings.
• Check fan casing
foreign matter on
inside.
Fan motor burnout
or foreign matter in
bearings.
45
Remove foreign
matter or repair.
Repair or replace.
Remove foreign
matter or repair.
Repair or replace.