Rotronic HS5 Short Instruction Manual

Digital hygrostat/thermostat
Hide thumbs Also See for HS5:

Advertisement

Available languages

Available languages

Quick Links

HS5 / H
/T
YGROSTAT
HERMOSTAT
SHORT INSTRUCTION MANUAL
Digital Hygrostat/Thermostat
Digital Hygrostat/Thermostat.
Congratulations on your new HS5 transmitter. Please
read these short instructions carefully before installing
the device.
General Description
These short instructions are limited to a description of
the main functions and installation of the device. The
detailed instruction manual can be found on the internet
at: www.rotronic.com.
Dimensions / Connections
Mechanical Installation
Relative Humidity and Temperature Measurement
Relative humidity is very temperature-dependent. In order to measure it exactly, the probes and
sensors must be set exactly on the temperature level of the environment that is to be measured.
The installation site can therefore have a signifi cant infl uence on the performance of the device.
Select an installation site where the humidity, temperature and pressure conditions are represen-
tative of the environments that are to be measured.
Orientation
Mount the transmitter so that the probe points down.
Mounting with Drill Template
Drill the necessary holes using the drill template
drawn on the packaging. Then insert the plugs
delivered with the device and mount the transmitter
with the screws.
Mounting on DIN Top-Hat Rail
The transmitter can be mounted directly on a TS35
DIN top-hat rail with the AC5002 mounting kit (order
separately). For this, the DIN holders are screwed
directly on to the pre-drilled holes in the transmitter.
Electrical Installation
Supply Voltage
Current Consumption
15...40 VDC
<100 mA
12...28 VAC 50/60 Hz
<450 mA
A
Caution!
Wrong supply voltages and excessive loads on the outputs can damage the transmitter.
Current output
OUT 1 = %RH
V+
OUT 2 = °C / °F
= ~
K 3
K2
1 2 3
V –
1
GND
V +
2
3
Voltage output
K4
V+
GND
4
B4
GND
3
OUT2
2
Ethernet
OUT1
1
GND
Terminal
Description
K2-1 GND
GND
K2-2 V+
Power supply +
K2-3
Protective ground
K3-1 NC
Relay: normally open (n.o.) connection
K3-2 COM
Relay: common connection
K3-3 NO
Relay: normally closed (n.c.) connection
K4-4 GND
GND
K4-3 GND
K4-2 OUT2
Analog output +, temperature
K4-1 OUT1
Analog output +, humidity
Terminal K1-3: Protective ground is connected to GND as standard. If this is not wanted, the solder
pad B4 on the PCB must be disconnected.
Service Interface / Ethernet
A
Caution!
Make sure that all settings have been made correctly before integrating and connecting
the HS5 in the network.
Display
MENU / One menu level back
ENTER
Increase value / Display line up
Decrease value / Display line down
Note
Unauthorized use of the menus can be blocked with the HW4 software.
HW4 Software > Device Manager > Display.
Menu Navigation
Menu Item
Submenu
Description
Device Settings
Units
Units
Backlight
Backlight
Contrast
Contrast input
Trend
Trend indicator
Pressure
Input ambient pressure
Function
Function
Row 3
3rd display line
OUT1
OUT2
Device Information
Version
Firmware version
GND
Serial No.
Serial number of the device
Address
Device address
OUT1
Type
Device type
OUT2
Name
Device name
Alarm Settings
GND
Alarm Low
Input of the bottom alarm
value
Alarm High
Input of the top alarm value
Hysteresis
Input of the switching
hysteresis
Relay
Relay function
Relay Off
Stop response
Probe Information
Version
Firmware version
Serial No.
Serial number of the probe
Address
Probe address
Name
Probe name
SensorTest
Sensor test
Record
Logging
Sensor-
Sensor type
Type
Humidity adjust
RefValue
Input adjustment value
Acquired
Number of adjustment
points
<Acquire>
Record adjustment point
<Delete>
Delete adjustment point
<Adjust>
Adjust
Temperature adjust
RefValue
Input adjustment value
<Adjust>
Adjust
Avoiding Sources of Error
Measured values can be compromised by the following infl uences:
Options
Temperature
• Through insuffi cient adaptation time, cold outer walls, heaters, direct sunlight, etc.
Metric / English
Humidity
Key Press / On / Off
• Through vapor, splashed water, dripping water or condensation on the sensor
• This does not impair the reproducibility or long-term stability, even when the probe is exposed
0...100
to high humidity or saturation with water vapor (condensation) for a prolonged period.
On/Off
Contamination
• By dust in the air
Thermostat or Hygrostat
The probe fi lter must be cleaned or replaced periodically.
Calc. / None
Scaling / Adjustment / Firmware Update
The following settings can be made with the help of the HW4 software and service cable AC3006
(use external power supply) or AC3009 (power supply via service cable):
• device settings
• fi rmware update
• adjustment
Periodic Calibration of the Probe / Transmitter
The device and its probe are very stable and do not normally need to be changed or calibrated
after factory calibration. For maximum accuracy we recommend regular calibration of the device
and probe.
Technical Data
Device type
Humidity / Temperature transmitter
Range of application
0...70 °C/0...100 %RH, non-condensing
0...60 °C (with display)
On/Off
Measurement ranges
0...100 %RH, -100...200 °C (probe-dependent)
Endless/End Alarm/
Accuracy humidity
Probe-dependent
Timeout/E. or T
Accuracy temperature
Probe-dependent
Inputs
HygroClip2 input, relay
Outputs
0 / 4...20 mA or 0...10 V (freely scalable)
Digital communication
Optional: Ethernet RJ45
Permissible load
>1 kΩ (voltage output)
<500 Ω (current output)
Maximum load
HW4 compatibility
V3.7.0 and later
Relay switching power
<50 VAC / <75 VDC / <1 A, confi gurable via HW4
On/Off
Housing material
ABS
Dimensions
129 x 45 x 96 (per technical drawing)
On/Off
Protection:
IP65 / IP40 (model with Ethernet)
Weight:
240 g
Detailed documentation can be found on the internet at: www.rotronic.com.
ROTRONIC AG, CH-8303 Bassersdorf
Tel. +41 44 838 11 44, www.rotronic.com
ROTRONIC Messgeräte GmbH, D-76275 Ettlingen
Tel. +49 7243 383 250, www.rotronic.de
ROTRONIC SARL, 56, F - 77183 Croissy Beaubourg
Tél. +33 1 60 95 07 10, www.rotronic.fr
ROTRONIC Italia srl, I- 20157 Milano
Tel. +39 2 39 00 71 90, www.rotronic.it
ROTRONIC Instruments (UK) Ltd, West Sussex RH10 9EE
Phone +44 1293 571000, www.rotronic.co.uk
ROTRONIC Instrument Corp, NY 11788, USA
Phone +1 631 427-3898, www.rotronic-usa.com
ROTRONIC Canada Inc.,Canada L8W 3P7
Phone + 1 905 754 5164, www.rotronic.ca
ROTRONIC Instruments Pte. Ltd., Singapore 159836
Phone +65 6376 2107, www.rotronic.sg
ROTRONIC Shanghai Rep. Offi ce, Shanghai 200233, China
Phone +86 40 08162018, www.rotronic.cn

Advertisement

loading

Summary of Contents for Rotronic HS5

  • Page 1 Make sure that all settings have been made correctly before integrating and connecting Detailed documentation can be found on the internet at: www.rotronic.com. The installation site can therefore have a signifi cant infl uence on the performance of the device.
  • Page 2 Funktion Thermo- oder Hygrostat Der Fühlerfi lter ist periodisch zu reinigen oder zu ersetzen. Stromausgang OUT 1 = %RH Wir gratulieren Ihnen zum Kauf Ihres neuen HS5 Mes- Row 3 3. Displayzeile Calc. / None OUT1 Skalierung / Justierung / Firmware-Update OUT2 sumformers.
  • Page 3 Poids 240 g L’humidité relative dépend fortement de la température. Pour une mesure exacte, le capteur et les Assurez-vous d’avoir correctement effectué tous les réglages avant d’intégrer le HS5 SensorType Type d’élément sensible éléments sensibles doivent être exactement à la température de l’environnement à mesurer. Le au réseau et de le raccorder.
  • Page 4 Logging On/Off sonde e sensori abbiano esattamente la stessa temperatura dell’ambiente da misurare. Pertanto Prima di inserire lo strumento HS5 in rete e di collegarlo, assicurarsi di aver effettuato SensorType Tipo di sensore la sede di installazione scelta ha un ruolo decisivo per il rendimento dello strumento.