Display; Parameter Setting; Display 7-1 Parameter Setting - HANMI TECHWIN TDC-9030 Operating Manual

Industrial battery charger
Table of Contents

Advertisement

7. Display

7-1. Parameter setting

7-1-1. Parameter type and description
Parameter
Auto Run
Batt. Voltage
Batt. Capacity
Output Current
Equalizing Time
*Max. Current
*Halt on WDR
Caution 1) In case of actual use after the test run, be sure to set Auto Run to
ON to charge the battery automatically.
Caution 2) The mark '*' can not be arbitrarily adjusted by the user.
① Auto Run : Set which mode to start at initial startup
- This parameter is used when the MCU starts to operate due to Power
ON or Reset. If it is set to OFF, start and stop of charging can be
controlled with the RUN key.
② Batt. Voltage : Set the battery voltage.
- If 18 batteries of 12V are used in series, set to 12 × 18 = 216 [V].
The Floating Charge charges 111% of the battery voltage and the
Equalized Charge charges the constant voltage / constant current to
117% of the battery voltage.
③ Batt. Capacity : Set the battery capacity.
- If the battery capacity is 100AH, setting 100 will automatically set the
parameter 'Max. Out Current' to 5A, which is the charging standard
for
20 hours.
④ Output Current : Sets the output current limit.
- Set the current that the charger can output at maximum. This limit
setting allows you to safeguard your battery and circuit, especially
when large currents can flow, such as a recovery charge.
⑤ Equalizing Time : Set the equal charge time.
⑥ *Max. Current : An overcurrent fault occurs when the charger exceeds
⑦ *Halt on WDR : Set or cancel the self-diagnosis function of the MCU.
7
Industrial Battery Charger TDC-9030
Setting
OFF / ON
OFF / ON
the set current.
Range
24 ~ 240 [V]
10 ~ 300 [AH]
1.0 ~ 30.0 [A]
30 ~ 180 [min]
1.0 ~ 30.0 [A]
HANMI TECHWIN. CO., LTD.
Default
OFF
216 V
100 AH
Capacity / 20
120 min
20.0 A
ON

Advertisement

Table of Contents
loading

Related Products for HANMI TECHWIN TDC-9030

Table of Contents