CONFIGURING THE SCF DRIVE
Entering Program Mode:
To access the parameters, press the Mode button. This will
activate the password prompt. The display will read "00" and the
right-hand decimal point will be blinking. Use the  and  buttons
to scroll to the password value (the factory default password is 225)
and press MODE to enter.
Press Mode
Display reads "00"
Upper right decimal point blinks
Use  and  to scroll to the password
value (factory default password is 225)
Press Mode to enter password
Once the PROGRAM mode is accessed, use the  and  buttons to
scroll to the desired parameter number, and press the Mode button
to see the parameter setting. Use the  and  buttons to change
the parameter setting and press Mode to store the new setting.
Connections:
Below is a sample wiring diagram for two-wire start/stop control. The
drive is ready to use right out of the box, with these simple control
wiring connections; no parameter adjustments are required. Speed
is controlled from the  and  buttons on the front of the drive.
1
2
5
6
11
12
2
14
13B
Run/Stop Contact
To add a potentiometer for speed control, change Parameter #5
(Standard Speed Source) to 0-10 VDC (03).
1
2
5
6
11
12
2
14
Speed Pot
Run/Stop Contact
SCF PARAMETER MENU
Parameter
No.
Name
01
Line Voltage
02
Carrier Frequency
03
Start Method
04
Stop Method
05
Speed Source
06
TB-14 Output
13
TB-15 Output
8
TB-30 Analog Out
9
TB-31 Analog Out
10
TB-13A Select
11
TB-13B Select
13C
12
TB-13C Select
14
Control
15
Serial Link
16
Units Editing
13B
13C
17
Rotation
19
Acceleration Time
20
Deceleration Time
21
DC Brake Time
22
DC Brake Voltage
23
Min Frequency
24
Max Frequency
25
Current Limit
Range of Adjustment
Factory Default
High (01), Low (02)
High (01)
4 kHz (01), 6 kHz (02),
6 kHz (02)
8 kHz (03), 10 kHz (04)
Normal (01), Start on Power-up
(02), Start w/DC Brake (03),
Auto Restart w/DC Brake (04),
Normal (01)
Flying Restart 1 (05), Flying Restart 2 (06),
Flying Restart 3 (07)
Coast (01), Coast with
DC Brake (02), Ramp (03),
Coast (01)
Ramp with DC Brake (04)
Keypad (01), Preset #1 (02),
Keypad (01)
0-10 VDC (03), 4-20 mA (04)
None (01), Run (02), Fault (03),
Inverse Fault (04), Fault Lockout (05),
At Set Speed (06),Above Preset #3 (07),
None (01)
Current Limit (08), Auto Speed (09),
None (01)
Reverse (10),
Min Alarm (11),
Max Alarm (12), Min/Max Alarm (13)
None (01), 0-10 VDC Freq (02),
2-10 VDC Freq (03),
None (01)
0-10 VDC Load (04),
2-10 VDC Load (05)
None (01), 0-10 VDC Load (02),
2-10 VDC Load (03),
None (01)
Dynamic Braking (04)
None (01), 0-10 VDC (02),
4-20 mA (03), Preset Speed #1 (04),
Run Reverse (05), Start Reverse (06),
External Fault (07), Remote Keypad (08),
None (01)
DB Fault (09), Auxiliary Stop (10),
Accel/Decel #2 (11),
Keypad Setpoint (12)
None (01), 0-10 VDC (02),
4-20 mA (03), Preset Speed #2 (04),
Decrease Freq (05), Jog Forward (06),
None (01)
Jog Reverse (07), Auxiliary Stop (08),
Keypad Setpoint (09)
None (01), 0-10 VDC (02),
4-20 mA (03), Preset Speed #3 (04),
Increase Freq (05), External Fault (06),
None (01)
Remote Keypad (07), DB Fault (08),
Accel/Decel #2 (09),
Keypad Setpoint (10)
Terminal Strip Only (01),
Terminal
Remote Keypad Only (02),
Strip (01)
Terminal Strip or Remote Keypad (03)
Disable (01),
9600, 8, N, 2 with Timer (02),
9600, 8, N, 2, without Timer (03),
9600, 8, N,
9600, 8, E, 1 with Timer (04),
2 with Timer (02)
9600, 8, E, 1, without Timer (05),
9600, 8, O, 1 with Timer (06),
9600, 8, O, 1, without Timer (07),
Tenths of Units (01), Whole Units (02)
Whole Units (02)
Forward Only (01), Forward and Reverse (02)
Forward Only (01)
0.1 - 3600.0 sec
20.0 sec
0.1 - 3600.0 sec
20.0 sec
0.0 - 3600.0 sec
0.0 sec
0.0 - 30.0 %
0.0%
0.0 - Max Frequency
0.0 Hz
Min Frequency - 240.0 Hz
60.0 Hz
30 - 180%
180%
Parameter
No.
Range of Adjustment
Name
26
Motor Overload
30 - 100%
27
Base Frequency
25.0 - 500.0 Hz
28
Fixed Boost
0.0 - 30.0%
29
Accel Boost
0.0 - 20.0%
30
Slip Compensation
0.0 - 5.0%
31-
Preset Speeds
0.0 - Max Frequency
37
38
Skip Bandwidth
0.0 - 10.0 Hz
39
Speed Scaling
0.0 - 6500.0
40
Frequency Scaling
3.0 - 2000.0 Hz
41
Load Scaling
10 - 200%
42
Accel / Decel #2
0.1 - 3600.0 sec
43
Serial Address
1 - 247
44
Password
000 - 999
45
Spd at Min Signal
Min Frequency - 999.0 Hz
46
Spd at Max Signal
Min Frequency - 999.0 Hz
47
Clear History
Maintain (01), Clear (02)
User Settings (01), OEM Settings (02),
48
Program Selection
Reset OEM (03), Reset 60 (04),
Reset 50 (05), Translate (06)
50
Fault History
View Only
51
Software Code
View Only
52
DC Bus Voltage
View Only
53
Motor Voltage
View Only
54
Load
View Only
55
0-10 VDC Input
View Only
56
4-20 mA Input
View Only
57
TB Strip Status
View Only
58
Keypad Status
View Only
59
TB-30 Output
View Only
60
TB-31 Output
View Only
Off (01), Normal 4-20 mA (02),
Normal 0-10 VDC (03),
61
PI Mode
Reverse 4-20 mA (04),
Reverse 0-10 VDC (05)
62
Min Feedback
0.0 - 999.0
63
Max Feedback
0.0 - 999.0
64
Proportional Gain
0.0 - 99.9 %
65
Integral Gain
0.0 - 99.9 sec
66
PI Accel/Decel
0.0 - 999.0 sec
67
Min Alarm
0.0 - 999.0
68
Max Alarm
0.0 - 999.0
69
0-10 VDC Feedback
View Only
70
4-20 mA Feedback
View Only
71
Actual Frequency
View Only
Items in blue are included with the PI option.
Factory Default
100%
60.0 Hz
1.0%
0.0%
0.0%
0.0 Hz
0.0 Hz
0
60.0 Hz
200%
20.0 sec
1
225
0.0 Hz
60.0 Hz
Maintain (01)
User Settings (01)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
Off (01)
0
100
5.0%
0.0 sec
20.0 sec
0
0
(N/A)
(N/A)
(N/A)