Magnelab Mini AC Current Transducer (CT) Connection Instructions
Configuring the Data Logger for the CT using HOBOware Software
HOBOware software provides configuration files for the CTs. The table below lists the recommended configuration values for
each CT that these files contain. For information on loading configuration files, refer to the software documentation.
Onset Part No:
Channel Name
T-MAG-0400-05
Current
T-MAG-0400-20
Current
T-MAG-0400-50
Current
T-MAG-0400-75
Current
Raw Value 1 (mV)
Raw Value 2 (mV)
0
333
0
333
0
333
0
333
2
Scaled Value 1
Scaled Value 2
0
5
0
20
0
50
0
75
Scaled Units
A
A
A
A