Magnelab Mini AC Current Transformer (CT) Connection Instructions
For use with HOBO
Applies to these Magnelab CTs
Onset Part No.
T-MAG-0400-05
T-MAG-0400-20
T-MAG-0400-50
T-MAG-0400-75
Installing CTs in an energized electrical enclosure or on any energized conductor can result in severe injury or death. These CTs
are for installation by qualified personnel only. To avoid electrical shock, do not perform any installation or servicing of these CTs
unless you are qualified to do so. Disconnect and lock-out all power sources during installation and servicing.
This document provides instructions on connecting the Magnelab CTs listed above to the
FlexSmart
™
TRMS Module used with either HOBO H22, U30, or RX3000 series data
loggers. It also lists configuration values used by HOBOware
logger for each CT.
Required
•
Selected Magnelab CT
•
HOBO H22, U30, or RX3000 series data logger
•
FlexSmart TRMS Module, Onset Part No: S-FS-TRMSA (for H22 series only) or
S-FS-TRMSA-D (for H22, U30, or RX3000 series)
•
HOBOware software, version 2.2.1 or higher (2.4.0 or higher for U30 series)
•
HOBOlink (for RX3000 series)
Dimensions
Dimensions
A
3.962 cm (1.56 in.)
B
2.54 cm (1.00 in.)
C
1.016 cm (0.40 in.)
D
2.54 cm (1.00 in.)
E
2.667 cm (1.05 in.)
© 2010–2016 Onset Computer Corporation. All rights reserved. Onset, HOBO, HOBOware, and HOBOlink are registered trademarks of Onset Computer Corporation.
Other products and brand names may be trademarks or registered trademarks of their respective owners.
14255-D MAN-MINI-CT-x
Find Quality Products Online at:
®
H22, U30, and RX3000 Series Data Loggers
Rated Current
Output
5 Amps
0-333mV AC representing 0 to 5 Amps AC
20 Amps
0-333mV AC representing 0 to 20 Amps AC
50 Amps
0-333mV AC representing 0 to 50 Amps AC
75 Amps
0-333mV AC representing 0 to 75 Amps AC
DANGER!
GlobalTestSupply
www.
Magnelab Part No.
SCT-0400-005
SCT-0400-020
SCT-0400-050
SCT-0400-075