8 channel ma input station

Advertisement

2300-A8II Specifications.
Current Inputs:
-Input Points
-Input Current
-Input Type
-1
-2
-3
-Drift
-Isolation
Connectors:
-Logic Power and Comms
-Inputs
Comms:
-Protocols
-Baud Rate
-Format
Power Supply: -Logic Supply Voltage
-Logic Supply Current
Safety and EMC Compliances:
EMC Compliance
Safety Compliance
General Specifications: (Unless otherwise stated in other input specifications.)
Operating Temperature
Storage Temperature
Operating Humidity
Housing
-Dimensions
-Mounting
Note 1.
Contact INTECH INSTRUMENTS for more detailed programming information.
Product Liability. This information describes our products. It does not constitute guaranteed properties and is not intended to affirm the
suitability of a product for a particular application. Due to ongoing research and development, designs, specifications, and documentation
are subject to change without notification. Regrettably, omissions and exceptions cannot be completely ruled out. No liability will be
accepted for errors, omissions or amendments to this specification. Technical data are always specified by their average values and are
based on Standard Calibration Units at 25C, unless otherwise specified. Each product is subject to the 'Conditions of Sale'.
Warning: These products are not designed for use in, and should not be used for patient connected applications. In any critical
installation an independent fail-safe back-up system must always be implemented.
2300-A8II Dimensions.
The 2300-A8II enclosure is shown below. The station clips directly onto an industry standard DIN rail. Field
wiring is on the top of the station via a separate plug in connector. The station power and RS485
communications wiring are on a separate plug in connector on the side of the housing.
Allow at least 25mm on front and below the station to accommodate the wiring. Ensure that enough space is
available above and below the station for good ventilation.
8
0(4) ~ 20 mA
Range
Resolution
0 – 4095
12 bits
0–20.000mA
1uA
+/-20.000mA
1uA
100ppm/°C
1000Vrms between field and logic
350Vpeak between each input
4 Pin plug-in connector on side of station
18 Way screw plug-in connector on top of station
RS485, Modbus RTU.
9600.
8 bit, No Parity, 1 Stop.
12~24Vdc
58mA @ 12V / 31mA @ 24V
89/336/EEC and Low Voltage Equipment Directive 73/23/EEC.
IEC 950.
-10~50˚C.
-40~85˚C.
Up to 95% non condensing.
L=97.5, W=22.6, H=109mm.
35mm Symmetrical Mounting Rail.
14.22-4
www.intech.co.nz