F-5500 Insertion and Inline
Thermal Mass Flow Sensor
Installation and Operation Guide
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699
www.onicon.com • sales@onicon.com
2030-2 /107023 Rev C
06-17

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the F-5500 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Onicon F-5500

  • Page 1 FLOW AND ENERGY MEASUREMENT F-5500 Insertion and Inline Thermal Mass Flow Sensor Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 www.onicon.com • sales@onicon.com 2030-2 /107023 Rev C...
  • Page 2: Model F-

    All ONICON Manuals and software available in English only. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 3: Table Of Contents

    8. Glossary of Terms and Abbreviations Page 94 9. Index Page 95 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 4 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 5 BACnet  CHG                            OK   only ID=12345 CHG                            OK   Name=F‐5500 CHG                            OK   11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 6 (See Flow Menu 2, p. 8, for more alarm settings) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 7 YES                              NO Zero CAL-CHECK ® Menu, p. 10 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 8 If that is the case, the alarm status will only be shown on the display,  LoFloAlm=0 °F through serial communication or F‐5000 View. CHG                            OK If the digital output is assigned to an alarm, changing the value here will  change that setting. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 9 • Alarm = Notification of errors; diagnostic errors 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 10    ZERO=2.321    ZERO=0.257   ZERO=0.911    Fail                        OK    Pass                        OK   Warning                   OK 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 11 Pwr_Cycl=24 Display 18 Err_tot=0 ZRO= 0.1 Display 19 F3 & F4 pressed at the same time will  initiate a "Total" reset 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 12: Introduction

    ONICON’s DDC-Sensor™ provides a technology platform for calculating accurate gas correlations. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 13 NOTE: the latest version of the F-5000 View software is available for download at http://www.onicon.com/F5500.html . 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 14 (Free F-5000 View Software) Outputs and Communications are Galvanically Isolated 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 15: Quick Start Guide

    A - D on the following page. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 16 If you are experiencing any problems after completing this procedure, please call the ONICON Service Department at 727-447-6140 to review this information. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 17: Installation (Mechanical)

    11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 18 • Follow the manufacturer's instructions to reduce the potential of an electrostatic charging hazard. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 19 ONICON provides flow conditioners as an optional accessory. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 20 The size of the flow conditioner must match the pipe size. Contact ONICON for Schedule 80 flow conditioners. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 21: Sensor Elements

    FLOW NOTE: Rotational misalignment must not exceed ±5°. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 22 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 23 8" 8.625" 7.981" 7.625" 3.261" 3.083" 18" 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 24: Compression Fittings

    Install the meter with the flow direction indicator pointing in the direction of flow in the pipe. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 25 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 26 Pro le FLOW Upstream Downstream Irregular Pro le 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 27 NOTE: ONICON does not supply gaskets for this product. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 28 90° increments (±180°). FLOW AND ENERGY MEASUREMENT 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 29: Wiring (Electrical)

    For signal and serial communication wiring, the recommended wire gauge is 18 to 22 AWG. Always use twisted pair shielded cable. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 30: Input Power

    • Supply connection wiring must be rated for at least 90°C. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 31: Signal Wiring

    • Some PLC and DCS equipment have built in load resistors, please refer to the technical manuals of such equipment. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 32 • Some PLC and DCS equipment have built in load resistors, please refer to the technical manuals of such equipment. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 33 RS485 Modbus RTU and BACnet MS/TP . 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 34 RS485 Modbus RTU and BACnet MS/TP . 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 35 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 36: Hart Wiring

    • Some PLC and DCS equipment have built in load resistors, please refer to the technical manuals of such equipment. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 37 12 to 28VDC Return HART Handheld Communicator 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 38 4-20mA *(see important note on previous page) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 39: Operation (Standard Operation)

    FLOW AND ENERGY MEASUREMENT Display Screen Mechanical (Push) Buttons 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 40 Enter programming screen Requires password. Default is 1234. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 41: Programming

    Press YES (F4) and the following screen will prompt user to enter password: PASWD:_ 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 42 Select NXT (F1) to select Flow or Temperature and then press OK (F4). 20 mA = 3500 SCFM 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 43 Press PUL (F2) to select the pulse output. The following screen will show: 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 44 Maximum pulse rate (frequency) is set to 1 Hz. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 45 Enter the value for the limit by pressing CHG (F1) and then OK (F4). 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 46 Display #1 Display #2 DSP2L1 DSP1L1 DSP2L2 DSP1L2 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 47 Press OK (F4) to accept selection. Press EXIT (F4) repeatedly until “Normal Mode” is seen briefly to exit the programming mode. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 48 Main Menu. To access the Unit Settings Menu: 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 49 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 50 After the pressure unit selection is made, the display will show a menu to enter the Pressure reference pressure: PresRef= 14.7 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 51 The first parameter is Flow Cutoff: CUTOFF = 2.0 SCFM 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 52 To set the parameters for a Low Flow Rate Alarm: Alarm LoFloAlm = 100 SCFM 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 53 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 54 Upon pressing OK (F4), an option to reset the NVRAM CRC will follow. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 55 If you are certain you want to activate the Non-resettable totalizer, select YES (F1). 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 56 Pressing DGN (F1) will show: DIAGNOSTIC ZERO EXIT 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 57 NOTE: Simulation Mode will be cleared if the power is cycled. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 58: Zero Cal-Check

    11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 59 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 60 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 61 ONICON Service at 727-447-6140 for assistance. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 62 2) Command 04: Read input register. 3) Command 06: Preset single register 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 63 Spare/ Not used 0x0F 40016 Status Status 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 64 <Meter Address> <Command code=04> <Byte count =2> <Status High><Status Low> <CRC high> <CRC low> 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 65 <Register address low=0x11> <Register data high=0x00> <Register data low =0x02> <CRC high> <CRC low> 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 66: Rs485 Modbus Rtu

    MAIN MENU EXIT 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 67 Press NXT (F1) repeatedly until the correct selection is shown and then press OK (F4) to accept the setting. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 68 NOTE: Power cycle is required for the new settings to take effect. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 69: Bacnet Ms/Tp

    LED indicator LP2 blinks when BACnet signals are received and LP1 blinks when BACnet signals are transmitted. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 70 This enters the programming mode: SET PARAMETERS? 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 71 Press NXT (F1) repeatedly until the correct selection is shown and then press OK (F4) to accept the setting. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 72 NOTE: Power cycle is required for the new settings to take effect. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 73: Hart

    Physical Device Transmitter, Category DC-isolated Bus Device 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 74 In Selected Units Elapsed Time In Hours 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 75 Damping is standard, affecting only the PV and the loop current signal. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 76 Catch Device Variable- This device does not support Catch Device Variable. Device-Specific Commands- No Device-Specific commands are implemented. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 77 Press NXT (F1) until HART is selected as shown and then press OK (F4) to accept the setting. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 78 ONICON Customer Service for technical assistance at 727-447-6140. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 79: Maintenance

    11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 80 If fuse is OK and unit still won’t power up, call ONICON for additional assistance 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 81 6. Re-install meter according to instructions (Refer to installation section, p. 18) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 82 • If the meter fails again, contact ONICON Technical Assistance at 727-447- 6140 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 83: Precautions

    Contact ONICON to discuss resolutions to this problem. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 84 ONICON Customer Service for alternatives. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 85 Refer to the RESET TOTAL section on p. 56 of this Manual to reset total. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 86: Specifications

    11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 87 Simulation mode used to align 4-20mA output and pulse output (if ordered) with the input to customer’s PLC/DCS. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 88: Agency Approvals

    Class 1, Zone 1, AEx/Ex db IIB + H2 T4; Gb Ta= -40˚C to 70˚C; Type 4X, IP66/67 www.onicon.com 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 89 [inches / millimeters] 15.0" (381 mm) 18.0" (457 mm) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 90: Dimensions

    18" 12.70" (323mm) 3.00" 18" 12.70" (323mm) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 91 18" 12.70" (323mm) 6.00" 24" 12.70" (323mm) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 92: Warranty

    EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 93: Returning Your Meter

    Rush recalibration service is available for a fee. Restrictions apply. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023...
  • Page 94 NIST National Institute of Standards and Technology 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 95: Index

    Precautions, p. 29 Product Description, p. 12 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page...
  • Page 96 Wiring Definition of Terms Troubleshooting Tips Information Caution - (refer to accompanying documents): Please follow the specified instructions and general safety practices. Indicates compliance with the WEEE Directive. Please dispose of the product in accordance with local regulations and conventions. Indicates compliance with the applicable European Union Directives for Safety and EMC (Electromagnetic Compatibility Directive...