Summary of Contents for Viega Basic Heating Control
Page 1
Radiant Basic Heating Control Installation Manual March 2009...
Page 2
The Viega Basic Heating Control is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset operation. The Basic Heating Control uses a floating action actuator mounted on a divert- ing or mixing valve to regulate the supply water temperature. The control has a Liquid Crystal Display (LCD) to view system status and operating information.
The Installation section (starting at 5.4 DIP Switch Settings) of this manual describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in Sections 3 and 4. VIEGA 1-800-976-9819...
1 second, the Displays when the system Item, buttons. The display circulator is in operation The Basic Heating Control uses a will then show the word ADJUst in Liquid Crystal Display (LCD) as the Burner the top right corner. Then select the method of supplying information.
2.1 General operation A 24 V (AC) floating action actuator motor is connected directly to When the Basic Heating Control is the Basic Heating Control on the powered up, the control displays the Com, Opn and Cls terminals (7, 8, control type number in the LCD for 2 and 9).
MIX DESIGN (MIX DSGN) (Sys Pmp, terminal 3) remains closed performing the heat loss calculations as long as the Basic Heating Control for the building. If a cold outdoor The MIX DSGN temperature is the is not in Warm Weather Shut Down.
BoILER ContRoL - CHAPtER 4 4 Boiler Control 4.1 Boiler operation When the Basic Heating Control determines that boiler operation is required, the Boiler contact terminals (5 and 6) close. While the Boiler contact is closed, the burner segment in the LCD is displayed.
Before removing the knockouts, representative for assistance. check the wiring diagram and select those sections of the chamber with The Basic Heating Control includes: common voltages. Do not allow the One Basic Heating Control, wiring to cross between sections as...
Page 9
The sensor should not When using the Supply Sensor with be exposed to heat sources such as a Viega Mixing or Injection Station, ventilation or window openings. insert the sensor into the immersion well on the elbow below the The Outdoor Sensor should be circulator pump.
Connections systEM CIRCULAtoR PUMP ContACts (sys PMP) The Sys Pmp output terminal (3) on the Basic Heating Control is a powered output. When the relay in the Basic Heating Control closes, 120 VAC is provided to the Sys Pmp terminal (3) from the Power L terminal (1). To...
Connect the two wires from the Supply Sensor to the Com and Mix terminals (10 and 11). The Supply Sensor is used by the Basic Heating Control to measure the supply water temperature downstream of the mixing or injection valve.
Page 12
Next, the actuator should move the valve to the fully closed position. If it does not, check the wiring between the terminals and the actuating motor. Refer to any installation or troubleshooting information supplied with the actuator. VIEGA 1-800-976-9819 PI-16015-03/09...
Injection Station and/or Diverting adjusted in the User Interface (see Valves, set DIP switch to “Station.” If Display Settings below). using Viega’s 3-4 Way Mixing Valves with Viega’s Mixing Valve Actuator 5.5 View Menu Display settings or the ProBloc, set DIP switch to “Bloc.”...
The desired room temperature. oUtDR DsGn The design outdoor temperature used for calculating heat-loss. Obtained from the Design Outdoor Temperature Chart, or Viega’s Radiant Wizard.* MIX DsGn The design supply water temperature obtained from the Supply Water Temperature / BTU Output Chart, or Viega’s Radiant Wizard.
See the following pages for the wiring may be shorted, there a good quality digital thermometer. a list of the Basic Heating Control’s may be moisture in the sensor, If a thermometer is not available, error messages and possible causes.
Ensure correct flow direction on all pumps. This is also a very useful step if additional assistance is required. VIEGA 1-800-976-9819 PI-16015-03/09...
Page 17
The control will continue to operate as if there was nothing connected to the Indoor sensor input. Locate the problem as described in Section 5.7. To clear the error message from the control after the sensor has been repaired, press the Item button. VIEGA 1-800-976-9819 PI-16015-03/09...
Page 19
MECHAnICAL AnD ELECtRICAL DIAGRAMs - CHAPtER 7 * three Position Actuator: White wire common, green wire open, brown wire close. Mixing Valve Actuator: Blue wire common, brown wire clockwise rotation, black wire counter-clockwise rotation VIEGA 1-800-976-9819 PI-16015-03/09...
Indoor use only, 32 to 102°F (0 to 39°C), <90% RH non-condensing Power Supply 120 VAC +/- 10% 50/60 Hz 1300 VA Floating Output 24 VAC 0.34 A 8 VA Relays 240 VAC 10 A 1/3 hp, pilot duty 240 VA Sensors NTC thermistor sensor Resistances VIEGA 1-800-976-9819 PI-16015-03/09...
Page 24
The global leader in plumbing and Viega heating systems. 301 N. Main Wichita, KS 67202 Rely on Viega for the most complete line Phone: 1-877-843-4262 of high tech/high quality plumbing, heating, 1-800-976-9819 Fax: 1-800-976-9817 and snow melting systems…plus the most comprehensive customer support in www.viega.com...
Page 27
3" priority Viega... The global leader in plumbing and heating systems. 301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 877-843-4262 • Fax: 800-976-9817 • E-Mail: service@viega.com • www.viega.com PI-PR-18060 (Zone Control) xxxxxx 0209 Plant ID No.9300-2856 Rev...
Page 28
120 VAC Viega... The global leader in plumbing and heating systems. 301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 877-843-4262 • Fax: 800-976-9817 • E-Mail: service@viega.com • www.viega.com PI-PR-18060 (Zone Control) xxxxxx 0209 Plant ID No.9300-2856 Rev...
Page 29
T200 Series Digital, On/Off Thermostat General Instructions Application T200 series thermostats provide temperature control on a variety of heating, cooling and single stage heat pump applications. The large LCD window displays room temperature including degree increments indicated by a series of dashes.
Page 30
SPECIFICATIONS Inputs Power Input: 20 to 32 Vac, 75 mA to 1.2 amps. Outputs Electrical: Battery, Setpoint backup (Energizer 357 or equivalent). Mechanical: Operating Differential, Heating 1 or 2F degrees (0.6 or 1.1C degrees), Cooling 2F degrees (1.1C degrees). Setpoint Adjustment Range, 50 to 86° F (10 to 30°C). Material, Rigid vinyl.
Page 31
TYPICAL APPLICATION (wiring diagram) DISPLAY HEATING OPERATING DIFFERENTIAL HEAT CONTROL COOL CONTROL AUTO CONTROL Figure-1 Terminal Identification. Table-2 Field Selectable Jumper Options. Feature Jumpered Not Jumpered 1. Display Celsius Fahrenheit 2. Heating operation differential 2 degrees 1 degree 3. Heat control No delay 5 minute delay 4.
Page 32
24 VAC TRANSFORMER 120 VAC 24 VAC Optional 250W 5 watt resistor is needed only if power drops below 75 milliamps. HEATING RELAY Figure-2 T201 Typical Wiring to Heating System With Single Transformer. 24 VAC TRANSFORMER 120 VAC 24 VAC COOLING RELAY RELAY...
Page 33
24 VAC HEATING TRANSFORMER 120 VAC 24 VAC FACTORY INSTALLED JUMPER HEATING 24 VAC COOLING RELAY TRANSFORMER 120 VAC COOLING RELAY If one of the secondary sides RELAY of both transformers are grounded, grounded sides must be connected together. Figure-5 Typical T205 Wiring to Heating/Cooling System With Dual Transformer. 24 VAC HEATING TRANSFORMER 120 VAC...
Page 34
Precautions General W A R N I N G • Electrical shock hazard! Disconnect power before installation to prevent electrical shock or equipment damage. • Make all connections in accordance with the electrical wiring diagram and in accordance with national and local electrical codes. C A U T I O N •...
Page 35
Mounting Mount the T200 series to a suitable surface. The T200 is shipped with an adapter plate (4-1/4 x 4-3/4 in.) that covers the mounting blemishes of a previous thermostat. New installation will not need the adapter plate. Do not mount on a surface that exceeds 125°F (52°C).
Page 36
CHECKOUT 1. Verify jumper pin selections. 2. Verify that the T200 is wired correctly to your heating and or cooling loads. 3. Confirm that 75 milliamps are available at all times. To measure the current draw connect an ammeter (set to measure milliamps) in series with the heat or cool output. If power value is below 75 milliamps install a 250 ohm 5 watt resistor in parallel across the switched load.
Page 37
VA transformer 1.54 in. This document subject to updates. For the most current Viega technical literature please visit www.viega.us. Click Services -> Click Electronic Literature Downloads -> Select Product Line -> Select Desired Document Viega LLC, 100 N. Broadway, 6 Floor •...