Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
WMAHV Single-Stage Cooling with Single- or 2-Stage Heating
Cooling Only—2-Stage Heat Thermostat
Module (If Used)
NOTES:
1. Y/Y2 enables high speed fan cooling.
2. E/W1 enables low speed fan heating. W/W2 enables high
speed fan heating.
3. OT1 PJ4 must be cut for this configuration.
Cooling Only—2-Stage Heat—1
NOTES:
1
st
Stage enabled through room thermostat.
nd
2
Stage enabled through closed outdoor thermostat.
1. Y/Y2 enables high speed fan cooling.
2. E/W1 enables low speed fan heating. E/W1 with outdoor
thermostat closed enables high speed fan heating.
10
Goodman 6 Long
Condensing Unit
To Comfort Alert
See Note 3
See Note 4
Please refer
to manual
for proper
DIP switch (CFM)
configuration.
st
Room Thermostat and 2
Outdoor Thermostat
Condensing Unit
To Comfort Alert
Module (If Used)
See Note 3
See Note 4
Please refer
to manual
for proper
DIP switch (CFM)
configuration.
WARNING
HIGH VOLTAGE!
Room Thermostat
nd
2
Stage Heater
st
1
Stage Heater
4. Cut HUM PJ6 jumper if using humidistat. Humidistat opens
on humidity rise.
5. DIP Switch 4 must be in the "ON" position.
nd
Outdoor Thermostat
Room Thermostat
nd
2
Stage Heater
1
st
Stage Heater
3. OT1 PJ4 must be cut for this configuration.
4. Cut HUM PJ6 jumper if using humidistat. Humidistat opens
on humidity rise.
5. DIP Switch 4 must be in the "ON" position.
Humidistat
(Optional)
See Note 4
Humidistat
(Optional)
See Note 4