8. SR100Hi– DC SETTINGS
Parameter
V nominal
V output (20°C)
BatDetect (mins)
Vpres:
Vbatl:
Vshutd:
Vdisco:
Bccl (%)
Comms
BCTim (mins)
CC Mins:
CC Hrs:
CC Days:
MfiBCT:
BatDetect:
Time between battery detections
Vpres:
Voltage threshold for battery detection and BCT. Note that if the voltage drops to this level dur-
ing a BCT the test is aborted and the BAT LOW alarm shows.
Vshutd:
Internal voltage level of the power supply during battery detection and battery condition tests.
Vbatl:
BAT LOW alarm voltage level
Vdisco:
Voltage at which the load is disconnected from the battery during mains fail
Bccl:
Battery charge current limit as percentage of the rated power supply current
Comms
Communication mode of PSU: F = continuous data stream of status
BCTim:
Length of battery condition test
CC Mins:
Time in minutes between automatically scheduled BCTs
CC Hrs:
Time in hours between automatically scheduled BCTs
CC Days:
Time in days between automatically scheduled BCTs
Note: The total time interval between battery condition tests (BCTs) is the sum total of the three 'CC' settings
MFiBCT:
Time in minutes before the mains fail check during the BCT (only applicable to SR100)
Scheduled BCT
disabled
SNMP VERSIONS ONLY:
Alarm mask
1048187
DHCP
enabled
Default Settings
12
24
30
13.8
27.6
34.5
60
60
60
12.2
24.4
30.5
11
22
27.5
11.5
23
28.7
10
20
25
100
100
100
M
M
M
20
20
20
40
40
40
23
23
23
27
27
27
30
30
30
Actual settings if different from default
36
48
41.4
55.2
60
60
36.6
48.8
33
44
34.5
46
30
40
100
100
M
M
20
20
40
40
23
23
27
27
30
30
8