EMERGENCY LIGHTING EQUIPMENT
! IMPORTANT SAFEGUARDS !
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. To prevent high voltage from being present on red & yellow output leads prior to installation, inverter
connector must be open. Do not join inverter connector until installation is complete and AC power is
supplied to the emergency ballast.
2. This product is for use with one (4') 32 W T8 bipin fluorescent lamp.
3. Make sure all connections are in accordance with the National Electrical Code and any local regulations.
4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and
inverter connector of the emergency ballast before servicing.
5. This emergency ballast is for factory or field installation in the ballast channel or on top of fixture.
6. This product is for use in indoor fixtures except air handling heated air outlets, and wet, damp, or
hazardous locations.
7. An unswitched AC power source is required (120 or 277 VAC, 60 Hz).
8. Do not install near gas or electric heaters.
9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
replaceable. Contact the manufacturer for information on service.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
CAUTION: Verify that all replacement lamp types marked on the installed luminaire are also identified as suit-
able for use with this inverter/charger pack.
THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.
236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.philips.com/bodine
SAVE THESE INSTRUCTIONS
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
© Philips Emergency Lighting
A Division of Philips Electronics North America Corporation
WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
Ni - Cd
08/01/13
70100194

Advertisement

loading

Summary of Contents for Philips bodine LP400

  • Page 1: Installation Instructions

    THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. 08/01/13 © Philips Emergency Lighting A Division of Philips Electronics North America Corporation 236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.philips.com/bodine 70100194...
  • Page 2 INSTALLATION WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST. NOTE: Make sure that the necessary branch circuit wiring is available.
  • Page 3 ILLUSTRATION 3A ILLUSTRATION 3B Fixture Fixture Charging Charging Indicator Indicator Light Light Violet (+) Violet (+) Brown (–) Brown (–) 1/2" White 5/8" Black 1/2" White 5/8" Black Bushing Bushing Bushing Bushing 1/2" Punch STEP 1 STEP 2 NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. If a detached charging indicator light is used, connect by matching wire colors and install as shown above.
  • Page 4 EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAMS FOR 1-lAMP EMERGENcy OPERATION FIG A ONE (1) LAMP INSTANT START BALLAST FIG B ONE (1) LAMP RAPID START BALLAST TO UNSWITCHED AC...