4297
Note: See the Installation & Setup Guide for the control panel being used for specific power and wiring requirements.
Figure 2. Typical Supplementary Power Supply Connections
CONTROL PANEL
• DO NOT CONNECT 4297 MODULES IN SERIES
(i.e., DO NOT CONNECT ONE MODULE'S EXTENSION
LOOP TO ANOTHER MODULE'S INPUT LOOP.)
DO NOT CONNECT MORE THAN EIGHT
4297 MODULES IN PARALLEL.
CONTROL PANEL
Figure 4. Typical Connections Using Multiple 4297 Modules
CONFIGURATION GUIDELINES
These guidelines apply to control panels that support V-Plex polling loop devices. Some of these control panels
may have additional limitations; refer to the control panel's Installation & Setup Guide for specific power and

wiring requirements.

Maximum number of devices:
• All input loops (combined) = 64 devices max.
• All input loops (combined) plus 1 output loop = 119 devices max.
Maximum wire length limits:
Refer to Table 1 (at right) for wire length per gauge,
and observe the maximum wire length limits.
• No individual wire run can exceed 2400 ft. max.
• 1 input loop plus 1 output loop (combined) = 4000 ft. max
• All input loops (combined) plus 1 output loop = 6400 ft. max
Note: Reduce wire length by ½ if using unshielded
wire in conduit, or if using shielded wire.
Maximum Current:
• All input loops (combined) = 128mA maximum current limit.
• Each output loop = 128mA
• Any single wire run = 64mA
INPUT POLLING LOOP (FROM CONTROL).
9
WHEN USING SUPPLEMENTARY POWER, ON
8
COMMERCIAL FIRE PANELS, DO NOT CONNECT
THE INPUT POLLING LOOP GROUND ON TERMINAL 7.
7
6
5
NO CONNECTION
4
3
2
1
+12VDC
POWER
INPUT POLLING LOOP
V-PLEX
V-PLEX
DEVICE
DEVICE
Figure 3. Connections Using One 4297 Module
INPUT POLLING LOOP
WIRE RUN LENGTH
MUST NOT EXCEED:
GAUGE
LENGTH
#22
100 FT
#20
150 FT
#18
225 FT
#16
375 FT
CURRENT DRAW:
• 50 mA + EXTENSION LOOP DRAW
DURING ACTUAL OPERATION.
• INCREASES TO 400 mA WHEN
EXTENTION LOOP SHORTENED
EXTENSION POLLING LOOP
V-PLEX
4297
DEVICE
4297
4297
Wire Gauge
#22
#20
#18
#16
- 2 -
NOTE
USE A CLASS II (POWER LIMITED) POWER
SUPPLY WHICH IS UL LISTED FOR THE
DESIRED FIRE AND/OR BURGLARY
APPLICATION. FOLLOW THE POWER SUPPLY'S
INSTRUCTIONS REGARDING BACKUP
BATTERY AND AC/BATTERY SUPERVISION
SIGNAL CONNECTIONS THAT APPLY TO THE
DESIRED APPLICATION.
TAKE CARE TO OBSERVE
POWER SUPPLY RATINGS.
SUPPLEMENTARY
POWER SUPPLY
+
USE CONTROL PANEL'S
AUXILIARY POWER OR USE
A SEPARATE POWER SUPPLY
4297-001-V0
TO
V-PLEX
OTHER
DEVICE
RPMS
polling_loop_005-V0
EXTENSION POLLING LOOP #1
V-PLEX
DEVICE
EXTENSION POLLING LOOP #2
V-PLEX
DEVICE
polling_loop-006-V1
Table 1
Wire Length
650 ft.
950 ft.
1500 ft.
2400 ft.