Raritan EMX series Quick Setup Manual page 6

Smart rack controller
Table of Contents

Advertisement

To set
Use this command
network <version>
IPv4 or IPv6
primaryDNSServer <ip address>
primary DNS
server
<ip address> = IP address of the primary
DNS server
network <version>
IPv4 or IPv6
secondaryDNSServer <ip address>
secondary DNS
server (optional)
<ip address> = IP address of the
secondary DNS server
9. To quit the configuration mode, type either of the following
commands, and press Enter.
Command
Description
apply
Save all configuration changes and exit.
cancel
Abort all configuration changes and exit.
The # prompt appears, indicating that you have quit the
configuration mode.
10. To verify whether all settings are correct, type the
following commands one by one.
Command
show network
show network ip all
show network
wireless details
Tip: You can type "show network wireless" to display
a shortened version of wireless settings.
11. If all are correct, type exit to log out of the EMX. If any
are incorrect, repeat Steps 7 to 10 to change network
settings.
QS R ule
Combining Asset Sensors
Each tag port on the asset sensors corresponds to a rack unit
and can be used to locate IT devices on a specific rack (or
cabinet). For each rack, you can attach asset sensors up to
64U long, consisting of one MASTER and multiple SLAVE
asset sensors. The difference between the master and slave
asset sensors is that the master asset sensor has an RJ-45
connector while the slave one does not.
Raritan EMX Quick Setup Guide
QSG-EMX-0I-v2.5.0  255-80-6106-00 RoHS
Description
Show network parameters.
Show all IP configuration
parameters.
Show all wireless parameters.
The following diagram illustrates some asset sensors. Note
that Raritan provides more types of asset sensors than the
diagram.
Number
Item
8U MASTER asset sensor with 8 tag ports
8U SLAVE asset sensor with 8 tag ports
5U "ending" SLAVE asset sensor with 5 tag
ports
Note: Unlike regular slave asset sensors, which have one DIN
connector respectively on either end, the ending slave asset
sensor has one DIN connector on only one end. An ending
asset sensor is installed at the end of the asset sensor
assembly.
To assemble asset sensors:
1. Connect a MASTER asset sensor to an 8U SLAVE asset
sensor.
Plug the white male DIN connector of the slave asset
sensor into the white female DIN connector of the
master asset sensor.
6