Default Power-Up State Of Reset Line; Reset Configuration Of Brains When Using Pamscan; Testing; Dip Switches (Pci-Ac51) And Jumpers (Pcie-Ac51) - OPTO 22 PCI-AC51 User Manual

Hide thumbs Also See for PCI-AC51:
Table of Contents

Advertisement

Default Power-Up State of Reset Line

When a computer with a PCI-AC51 or PCIe-AC51 card installed has just been powered up, bit 0 of
the reset control register will be in its default power-up condition, which is a bit value of zero. This
drives the reset line HIGH and turns LED 1 (reset line) ON.

Reset Configuration of Brains When Using PamScan

One of the parameters you must choose when using the PamScan utility is the reset level of the
brains in your system. Set the option in PamScan to match how your Pamux brains are configured.
PamScan needs to know the brain configuration so that it can determine whether to set the reset
line HIGH or LOW in order to take the system out of reset. This allows PamScan to configure and
control the brains and output modules.

Testing

The following table shows the results of using each of the possible reset settings on the brains and
in the PamScan utility. After choosing the reset setting in PamScan, click Connect to establish
communication with the PCI-AC51 or PCIe-AC51 card and brains.
Jumper 7 Setting
Set "Active Low"
Set "Active Low"
Set "Active High"
Set "Active High"

DIP Switches (PCI-AC51) and Jumpers (PCIe-AC51)

DIP switches or jumpers are provided on the adapter cards for custom implementation and some
Pamux settings.
DIP switches and jumpers may be modified on a system that is powered; however, the applications
that use the PCI-AC51 or PCIe-AC51 must be stopped.
Switches or jumpers 1 through 4 are provided for custom implementation. One common use will be
for identifying certain cards in a multiple card system. The settings of these switches or jumpers do
not affect the Pamux operation.
Pam Scan
on Brains
Configuration
Choose "Active Low"
Choose "Active High"
Choose "Active Low"
Choose "Active High"
The PCI-AC51 has six DIP switches (the DS1 bank). A switch in the ON position reads as a zero
and OFF reads as a one. The card is shipped with all switches in the ON position.
The PCIe-AC51 has eight jumpers (labeled JP2), of which only the first six are used. A jumper
removed reads as a zero, and a jumper in place reads as a one. The card is shipped with jumpers
removed. (Do not use the jumper group labeled J3. See the diagram on
group location.)
APPENDIX C: PCI-AC51 AND PCIE-AC51 TECHNICAL REFERENCE
Reset Line
State of
Voltage
Reset Line
3.48 VDC
HIGH
0 VDC
LOW
3.48 VDC
HIGH
0 VDC
LOW
PCI-AC51 and PCIe-AC51 User's Guide
Status
Brains allow control of outputs
Brains are reset
Brains are reset
Brains allow control of outputs
page 25
for jumper
33
33

Advertisement