Direct Connection

Connect the transducer directly to the Milltronics transceiver via the two conductor shielded
cable.
When connecting to an EnviroRanger ERS 500, a MultiRanger 100/200, or a
Note:
HydroRanger 200, the white, black, and shield wires are all connected separately. DO NOT
tie the white and shield wires together.

Coaxial Connection

Connect the transducer to the Siemens Milltronics transceiver via a junction box and RG–62 A/
U coaxial cable. This setup is effective for combined runs up to 365 m (1200 ft).
When connecting to an EnviroRanger ERS 500, a MultiRanger 100/200, and
Note:
HydroRanger 200, DO NOT use coaxial cable. See diagram below for proper procedure.

2-Wire Extension

(for EnviroRanger ERS 500, MultiRanger 100/200, and HydroRanger 200 only)
wht
7ML19985QT81
XRS-5 Series Transducers – OPERATION MANUAL
w
b
h
l
t
k
/
/
s
h
h
o
l
t
d
blk
blk
junction box
extend cable using 18 AWG shielded/twisted pair
wht
drain/shield
extend cable using RG-62 A/U coax
drain/shield
Page EN-7