iDM HYGIENIK 2.0 Installation Instruction

iDM HYGIENIK 2.0 Installation Instruction

With hot water station
Hide thumbs Also See for HYGIENIK 2.0:

Advertisement

Te c h n i c a l d o c u m e n t a t i o n
I n s t a l l a t i o n i n s t r u c t i o n
THE ENERGYFAMILY
H Y G I E N I K 2 . 0
W I T H H O T WAT E R S TAT I O N 2 . 0
HEAT PUMPS FROM AUSTRIA
www.idm-energie.at

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HYGIENIK 2.0 and is the answer not in the manual?

Questions and answers

Summary of Contents for iDM HYGIENIK 2.0

  • Page 1 I n s t a l l a t i o n i n s t r u c t i o n THE ENERGYFAMILY H Y G I E N I K 2 . 0 W I T H H O T WAT E R S TAT I O N 2 . 0 HEAT PUMPS FROM AUSTRIA www.idm-energie.at...
  • Page 2: Table Of Contents

    3. T ECHNICAL DATA YGIENIK 4. I NSTALLATION 4.1. Installation conditions for the Hygienik 2.0 4.2. Installation location of the Hygienik 2.0 4.3. Connecting sockets of the Hygienik 2.0 4.4. Installing the insulation jacket with a hook strip 5. I NSTALLING THE HOT WATER STATION 5.1.
  • Page 3 7.2. List of installation layouts 7.2.1. TERRA SW Complete + Hygienik 2.0 + direct heating circuit N_2.19-0-2-0-3-0 7.2.2. TERRA SW Complete HGL + Hygienik 2.0 + direct heating circuit N_1.3-0-2-0-3-0 7.2.3. TERRA SW Complete + Hygienik 2.0 + 3 heating circuits N_2.19-0-1-0-1-0 7.2.4.
  • Page 4: General Information

    1 .2. Sa fe ty in s tru ct i o ns Installation and maintenance work can be associated Only original iDM spare parts or spare parts comply- with dangers resulting from high system pressures, ing with iDM specifi cations may be used! high temperatures and live parts and may only be carried out by specialist staff.
  • Page 5: Information On Environmental Protection

    General information 1 .8 . In f or mat io n o n en v iro n men tal p ro - In the case of hot water modules from iDM Energie- t ect io n systeme, the following limit values prescribed by the manufacturer of the plate heat exchangers must be 1 .9 .
  • Page 6: Description

    The hot water station can either be mounted directly The primary circuit pump is activated via a fl ow switch on the Hygienik 2.0 or on a wall. This means it is also in the cold water line. possible to operate the hot water station with a tank made by another manufacturer.
  • Page 7: Notes On Dimensioning

    “Single tapping volume” This is the total quantity of hot water at 45 °C that can be tapped from a Hygienik 2.0 when the tank is 1...UVR 61-3 HEP speed controller (accessory) heated to 60°C right to the bottom and is not reheated 2...High-effi...
  • Page 8: Technical Data Hygienik

    Pressure loss on the drinking water side: approx. 0.3 bar Max. operating pressure on the heating side: 4 bar Max. operating pressure on the drinking water side: 6 bar Max. operating temperature: 90°C (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 9 Tapping volume per bathtub outlet: 10 l/min. at 45°C; per shower: 8 l/min. at 42°C Simultaneity factor: 1.5 times as high as that given in Handbuch für Heizung, Lüftung, Klima, Recknagl-Sprenger. Sport facilities: Tapping volume per shower: 8 l/min. at 42°C Simultaneity factor: 0.9 (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 10 Tapping temperature 45°C Cold water temperature 15°C at a storage tank charging temperature of 70°C the Hygienik 2000 l is also available with fl ange connection as Hygienik 2000 Max 2.0, see page 16 (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 11 Flow HGL resp. domestic hot water Drainage R ½“ R 1 ½“ or fl ow circulation station Sensor terminal Flow, heat pump R 1 ½“ Mounting, hot water station Return, heat pump R 1 ½“ (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 12 Flow HGL resp. domestic hot water Drainage R ½“ R 1 ½“ or fl ow circulation station Sensor terminal Flow, heat pump R 1½“ Mounting, hot water station Return, heat pump R 1½“ (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 13 Flow HGL resp. domestic hot water Drainage R ½“ R 1½“ or fl ow circulation station Sensor terminal Flow, heat pump R 1½“ Mounting, hot water station Return, heat pump R 1½“ (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 14 Flow HGL resp. domestic hot water R 1½“ Sensor terminal Flow, heat pump R 2“ Mounting, hot water station Return, heat pump R 2“ Flow, second heat generator / Solar R 1½“ (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 15 Flow HGL resp. domestic hot water Drainage R ½“ R 1½“ / 2” Sensor terminal Flow, heat pump R 2“ Mounting, hot water station Return, heat pump R 2“ Flow, second heat generator / Solar R 1½“ (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 16 R 1 1/4” Warm water station return R 1 1/4” Electric heating immerser (2x) R 2“ Circulation (2x) 2” Sleeve R 2 1/2“ Venting R 1/2“ Drainage 1/2” Holding for warm water station (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 17 Technical data Notes: (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 18: Installation

    4 .1. In st all at i o n c on d i ti o ns f o r t h e H y g ie - ni k 2 .0 By selecting a decentralized position for The iDM Hygienik 2.0 should be installed as close as the hot water stations near the tapping possible to the drinking water tapping points to keep points (e.g.
  • Page 19: Installing The Insulation Jacket With A Hook Strip

    For easier installation and to prevent the tank the equipment identifi cation sticker on the tank body tilting, have a second person lift the tank slightly. using the sensor terminal block. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 20 Store the insulation jacket in a warm room prior to installation, or wait until the tank has heated before closing the hook fastening strip! Pull the insulation jacket on carefully to avoid damaging it! (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 21 Fit these as required. We recommend that you insulate and cover connections that are not used, as this can reduce heat losses. Plug Insulating material made of fl eece Polystyrene covers (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 22: Installing The Hot Water Station

    The 25 l or 35 l hot water stations can either be mounted directly on the Hygienik 2.0 or on the wall. The 50 l hot water station can be mounted on the Hygienik 2.0 with a capacity of 1000 l, 1500 l and 2000 l.
  • Page 23: Installing The Hot Water Station On The Hygienik

    fi xed on the mounts by two delivered screws. The hot Fit the Armafl ex insulation supplied over the corrugat- water station is hooked into the holder must be fi xed ed hoses before connecting them to the Hygienik 2.0. with the third included screw below. (C) IDM ENERGIESYSTEME GMBH...
  • Page 24: Installing The Hot Water Station On The Wall

    fi tting is capable of bearing the weight of the mounted hot water station during op- eration. Working from the front, slide the iDM cover hood onto Retaining screw the hot water station in straight position until it snaps When the hot water station is mounted on the wall into place.
  • Page 25 The ball valves shown below are included in the scope of delivery of the 50 l and 70 l hot water stations. It is essential to fi t these valves on the construction site if the hot water stations is to be mounted on the wall and not on the Hygienik 2.0. Tank fl ow Hot water fl...
  • Page 26: Installing The Circulation Module

    The circulation pipe is routed under the return line of the hot water station. Remove the plug on the return line connection and connect the circulation pipe here. Using side cutting pliers, remove the perforated metal sheet over the recess for the circulation pump. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 27 Fit the ball valve provided onto the pump. Mount the circulation pump on the circulation pipe and attach to the bracket near the ball valve. It is essential to observe the fl ow direction when installing the circulation pump. Ball valve Circulation pump Circulation pipe Fully assembled circulation module (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 28: Installing The Heat Meter

    The temperature sensor of the heat meter is installed in the tank fl ow. Mount Operating unit The mount for the operating unit is attached at the side. The operating unit is attached with a screw-on connec- tion. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 29: Installing The Uvr 61-3 Hep Controller

    Remove the operating unit of the controller and fi x the housing to the bracket using the two fi xing screws. Then replace the operating unit. The controller, the pump and the sensor are connected as shown in the circuit diagram. The circuit diagram is enclosed with the UVR 61-3 HEP. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 30: Connecting To The Hot Water Station On The Drinking Water Side

    5 .7. Co n n ect in g t o t h e h ot w at er s t at io n o n optional iDM circulation module for the th e dr i n kin g w at e r s ide 25 l and 35 l hot water stations.
  • Page 31: Programming The Uvr 61-3 Hep

    Note: The parameters are set at the factory for use with the IDM hot water module. Only the desired hot water temperature should be changed if required! When using a solar plant, Program 640 in the enclosed instructions must be confi...
  • Page 32 • Does the pump run if the white contact of the fl ow switch is bridged? • If the controller is not in operation although the mains voltage is connected, the fuse (3.15 A fast-acting) should be checked and replaced if necessary. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 33 The menu “PAR” (see next page) primarily contains the installation layout (program number) and is used to set the solar differential temperature control. The menu “MEN” contains descriptions of the settings for the plate heat exchanger pump speed control. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 34 Change MAX limitation switch-off threshold for sensor T2 (tank sensor), fac- tory setting 90°C, as follows: Press ▼, display begins to fl ash Change setting with Save setting with , display stops fl ashing Press ► (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 35 Change Min limitation switch-on threshold for sensor T3 (not assigned), factory set- ting 45°C, as follows: Press , display begins to fl ash Change setting with Save setting with , display stops fl ashing Press ► (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 36 Press , minute display begins to fl ash 16.24 Change setting with Press , hour display begins to fl ash Save setting with , display stops fl ashing Press ► (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 37 Press ► For circulation, set AGU2 and the start and end time ZEITF Press ► For circulation, set AGU2 and the start and end time (The time windows should be set, otherwise 24h circulation) (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 38 , display begins to fl ash AUTO Change setting with (OFF or ON) Return with , display stops fl ashing Press ► AUTO AUTO End or start of the “PAR” menu: CODE32 Press ▲ (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 39 AV1 1.0 = Averaging for sensor S1 over 1.0 seconds (= factory setting) SYM 51 To change: Press , display begins to fl ash Change setting with Save setting with , display stops fl ashing Press ► (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 40 To change: Press , display begins to fl ash Change setting with Save setting with , display stops fl ashing Press ► S5 KTY Sensor S5 (hot water sensor) is of type KTY (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 41 , display begins to fl ash Change setting with Save setting with , display stops fl ashing Press ▲ until “ENTER“ appears, the current temperatures can be displayed by pressing ► ..˚C ENTER (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 42 Confi rm with . The display stops fl ashing Press SENSOR ANLGSF ST ARTF NACHLZ Pump speed control Press Absolute value control inverse operation is not activated at the factory ST AG Press (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 43 Change setting with Confi rm with . The display stops fl ashing Press Differential control, factory setting: switched off Press Set value of the differential control, factory setting: 40°C SW D 40 (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 44 Derivative component of the PID_controller, factory setting: 3 To change: Press , display begins to fl ash DIF 3 Change setting with Confi rm with . The display stops fl ashing Press (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 45 Current speed stage for Testing the plate heat exchanger pump, TST 100 To change: Press , display begins to fl ash Change setting with Confi rm with . The display stops fl ashing Press 5x to exit setting mode (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 46 PWM - pump (Yonos Para) Confi guration menu → Fresh water Minimum speed 20 % 0-10V - pump (Stratos Para - T2) Confi guration menu → Fresh water Minimum speed 30 % (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 47: Installation Layouts

    Heat distribution system (low-temperature heating) Legend and notes on the installation layouts Circulation pump Solutions from iDM are designed to offer the broadest 3-way mixing valve (without bypass), motor drive possible range of applications for heat pumps. Both 3-way mixing valve, thermal activation innovation through diversity and the use of already ex- isting heat generation systems are key considerations.
  • Page 48: List Of Installation Layouts

    System code Chapter TERRA SW Complete + Hygienik 2.0 + direct heating circuit N_2.19-0-2-0-3-0 7.2.1 TERRA SW Complete HGL + Hygienik 2.0 + direct heating circuit N_1.3-0-2-0-3-0 7.2.2 TERRA SW Complete + Hygienik 2.0 + 3 heating circuits N_2.19-0-1-0-1-0 7.2.3 TERRA SW Complete HGL + Hygienik 2.0 with LSP and circulation...
  • Page 49 (without layer separation plate) brine circuit Only one heating circuit is possible. The heating circuit must be designed as a pump circuit (no mixer!) and no zone bal- ancing valves may be used! (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 50 The underfl oor circuits must always remain open, zone valves may only be installed for approx. ¼ of the area. Temperature fl uctuations occur in the fl ow due to the heat pump switching on and off. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 51 The center tank connection is used as a buffer tank for heating operation. A Hygienik with layer separate plate is required. The heating return and the heat pump return must be fed separately into the Hygienik storage tank. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 52 A Hygienik with layer separate plate is required. The heating return and the heat pump return must be fed separately into the Hygienik storage tank. Circulation allows a higher hot water temperature to be achieved. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 53 7 . 2.5. A er o IL M C om pl et e H G L + H yg ienik 2 . 0 + Te r mo N_ 1. 12 - 7- 2 - 5- 1- 0 RE (A) HC-module internal availabel as accessory HC (A) Throttle valve B3 B35 M 22 B3 B34 4 AERO ILM HGL Hygienik 2.0 Termo (without layer separation plate) (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 54 7 .2. 6. TERRA ML 8 - 18 Com p le t e HG L + Hyg ie ni k 2. 0 N_ 1. 4 - 7- 1- 0 - 1- 0 HC-module RE (A) internal availabel as accessory HC (A) Throttle valve B B 3 M 22 B3 B38 Refrigerant pipes Outdoor unit Indoor unit Hygienik 2.0 (with layer separation plate) (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 55 7 . 2.7. T ERRA AL Tw in + Hyg ie n ik 2 .0 wit h L S P N_ 2. 1 3- 7- 1 - 0- 1 - 0 HC-module RE(A) internal availabel as an accessory HC(A) Switch cabinet Throttle valve M 22 TERRA AL Twin Hygienik 2.0 (with layer separation plate) (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 56: Terra Al 60 Max + Hygienik 2.0 + Termo N_2.14-7-2-5-1-0

    Installation layouts 7 .2. 8. TERRA AL 6 0 M ax + Hyg ie n ik 2.0 + Te r mo N_ 2 . 14- 7 - 2- 5 - 1- 0 (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 57: Heating Water

    The pH value should lie between 8.2 tures for the consumers, limescale formation can be and 9.5. distributed evenly and in a targeted manner over the heat exchanger surfaces of the boiler. (C) IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2.0...
  • Page 58: Repairs

    8. 7 . Cl e ani ng a nd de c al ci fi ca t io n in t er v al s Should it become necessary to drain the Hygienik 2.0 The plate heat exchanger of the hot water station must in order to carry out repair work, the system must be be decalcifi...
  • Page 59 UID-Nr.: ATU 433 604 02 Declaration of Conformity IDM-Energiesysteme GmbH, Seblas 16-18, A-9971 Matrei in Osttirol, confirms that the device(s) listed below, in the form marketed by us, fulfill(s) the requirements of the EC Directives, EC safety standards and product-specific EC standards. This Declaration shall become null and void if modifications are made to the device(s) without our approval.
  • Page 60 PRAXISWISSEN FÜR VERKAUF UND TECHNIK The comprehensive range of seminars for sp ecialists at the IDM POWER FA MILY is available to you any time on our websit. We look for ward to re ceiving your re gist ration. YOUR iDM PARTNER:...

Table of Contents