7.6 - Alarm codes

The alarm codes are displayed in the Reset Alarms menu,
while the Current Alarms menu and Alarm History /
Major Alarm History include the description of the alarm.
7.6.1 - General/major alarms
JBus
Alarm
Alarm description
code
code
THERMISTOR FAILURE
1
15001
Evaporator entering water thermistor fault
2
15002
Evaporator leaving water thermistor fault
3
15010
OAT thermistor fault
5
15011
Master/slave common water thermistor fault
6
15012
Suction gas thermistor fault, circuit A
7
15013
Suction gas thermistor fault, circuit B
8
15015
Discharge gas thermistor fault, circuit A
9
15016
Discharge gas thermistor fault, circuit B
10
15018
Condenser subcooling liquid thermistor fault, circuit A
11
15019
Condenser subcooling liquid thermistor fault, circuit B
16
15021
Space temperature thermistor fault
4
15023
Evaporator heater feedback thermistor fault
14
15024
Economizer gas thermistor fault, circuit A
15
15025
Economizer gas thermistor fault, circuit B
12
15033
Compressor motor thermistor fault, circuit A
13
15034
Compressor motor thermistor fault, circuit B
TRANSDUCER FAILURE
17
12001
Discharge transducer fault, circuit A
18
12002
Discharge transducer fault, circuit B
19
12004
Suction transducer fault, circuit A
20
12005
Suction transducer fault, circuit B
21
12010
Oil pressure transducer fault, circuit A
22
12011
Oil pressure transducer fault, circuit B
23
12013
Economizer pressure transducer fault, circuit A
24
12014
Economizer pressure transducer fault, circuit B
25
12024
Water pressure 1 transducer failure (before the pump)
26
12025
Water pressure 2 transducer failure (after the evaporator)
27
12029
Low water pressure
28
12031
Condenser subcooling liquid pressure transducer, circuit A
29
12032
Condenser subcooling liquid pressure transducer, circuit B
COMMUNICATION FAILURE
30
4901
Communication loss with SIOB board, circuit A
31
4902
Communication loss with SIOB board, circuit B
32
4501
Communication loss with Auxiliary Board Number 1
33
4502
Communication loss with Auxiliary Board Number 2
34
4503
Communication loss with Auxiliary Board Number 3
36
4603
Communication loss with Energy Management NRCP2 board As above
37
4701
Communication loss with VLT Board Number 1
38
4702
Communication loss with VLT Board Number 2
39
4704
Communication loss with Fan A1 Drive board
40
4705
Communication loss with Fan A2 Drive board
41
4706
Communication loss with Fan A3 Drive board
42
4707
Communication loss with Fan B1 Drive board
43
4708
Communication loss with Fan B2 Drive board
44
4709
Communication loss with Fan B3 Drive board
PROCESS FAILURE
45
10001
Evaporator freeze protection
46
10005
Low suction temperature, circuit A
47
10006
Low suction temperature, circuit B
52
10014
Customer safety loop failure
78
10090
Flow controller configuration fault
79
10091
Flow controller fault
53
10030
Master/slave communication failure
Reset type
Action taken
Automatic, if thermistor
Unit shuts down
reading returns to normal
As above
Unit shuts down
As above
Unit shuts down
Master/slave operation is
As above
disabled and the unit returns to
the stand-alone mode
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
None
As above
None
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
Automatic, if sensor voltage
Circuit A shuts down
reading returns to normal
As above
Circuit B shuts down
Automatic (three alarms in
Circuit A shuts down
the last 24 hours) or Manual
As above
Circuit B shuts down
Automatic, if sensor voltage
Circuit A shuts down
reading returns to normal
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
None or unit and pump shut
Automatic
down
As above
Circuit A shuts down
As above
Circuit B shuts down
Automatic, if communication
Unit shuts down
is re-established
As above
Unit shuts down
As above
None
As above
None
As above
None
None
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit A shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit B shuts down
As above
Circuit B shuts down
Automatic (the first alarm in
Unit shuts down, but the pump
the last 24 hours) or Manual
continues to run
As above
Circuit A shuts down
As above
Circuit B shuts down
Automatic (the first alarm in
Unit shuts down
the last 24 hours) or Manual
Manual
Unit shuts down
Automatic (the first alarm in
Compressors and the
the last 24 hours) or Manual
evaporator pump are stopped
As above
Unit shuts down
Possible cause
Defective thermistor
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
Defective transducer or
installation fault
As above
As above
As above
As above
As above
As above
As above
As above
As above
Water loop pressure
too low, risk of pump
cavitation
Defective transducer
As above
Bus installation fault or
defective board
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
No water flow,
defective thermistor
Pressure sensor
defective, EXV blocked
or lack of refrigerant
As above
Customer interlock
input set on
Defective flow
controller or wiring error
As above
As above
29