Installation / Service Tools; Specifications; Optional Parts, Accessories - Toshiba RAS-4M27U2AVG-E Installation Manual

Multi-split type inverter outdoor unit
Hide thumbs Also See for RAS-4M27U2AVG-E:
Table of Contents

Advertisement

Outdoor Unit
2

Installation / service tools

Changes in the product and components
In air conditioners using R32, in order to prevent any other refrigerant from being accidentally charged, the service port diameter size of the outdoor unit
service valve has been changed. (1/2 UNF 20 threads per inch)
• In order to increase the pressure resisting strength of the refrigerant piping, flare processing diameter and opposing flare nuts sizes have been changed. (for
copper pipes with nominal dimensions 1/2 and 5/8)
Gauge manifold for R32
Charge hose for R32
Vacuum pump for R32
Gas leakage detector for R32
3
Specifications
Cooling operation
Operating conditions*
1
Dry operation
Heating operation
Height
Dimension
Width
Depth
Net weight
Refrigerant R32
Power supply
Maximum running current
Installation fuse rating
Power cord (H07RN-F or 60245IEC66)
Connecting cable (H07RN-F or 60245IEC66)
Minimum for 1 unit
Maximum for 1 unit
Pipe length
Maximum for total unit
Height difference
No additional refrigerant charge
Refrigerant adjustment
The specifi cations for performance of this air conditioner differs depending on the combination of the indoor units which are operated.
The information in this specifi cations table applies for the combinations with the catalogue.
For operation, read the owner's manual packed with the indoor unit.
Equipment complying with IEC 61000-3-12.
*1 If the air conditioner is used in conditions other than the above, the safety protection functions may be activated.
* Example of indoor unit class: RAS-10PKVSG-E is abbreviated as "10".
E
05 or 07 or 10 or 13
D
05 or 07 or 10 or 13
C
05 or 07 or 10 or 13 or 16
B
05
*3
or 07
*3
or 10
A
05
*3
or 07
*3
or 10
68 (RAS-5M34U2AVG-E )
Total
54 (RAS-4M27U2AVG-E )
54 (RAS-3M26U2AVG-E)
4
  O ptional parts, accessories
Optional parts
Parts name
Indoor unit
(abbreviation)
Refrigerant piping
*4
05, 07, 10, 13
16, 18, 22, 24
Putty, PVC tapes
Accessories
Rubber cap
Installation
1
manual
(Water-proof)
Product
1
specifi cation
Phillips screwdriver
Level
Scale
Utility knife
Indoor unit class
*2
*3
or 13
*3
or 16 or 18 or 22 or 24
*3
or 13
*3
or 16 or 18 or 22 or 24
Specifi cations
Liquid side
Gas side (O.D.)
(O.D.)
6.35 mm
9.52 mm
6.35 mm
12.7 mm
CD-ROM
5
(Installation
manual)
Pipe cutter
Torque wrench
Wrench (or spanner)
Reamer
RAS-5M34U2AVG-E
RAS-4M27U2AVG-E
78 kg
2.39 kg
1 ph, 50 Hz, 220-240 V
19.5 A
20 A breaker or fuse (all types can be used)
3-core 2.5 mm
4-core 1.0 mm
80 m
20 g/m (41 m-80 m)
Standard connecting pipe diameter
6.35, 9.52 mm
6.35, 9.52 mm
6.35, 9.52 mm
6.35, 12.7 mm
6.35, 12.7 mm
*4 Refrigerant piping covered with insulating material (Polyethylene
Q'ty
form, 6 mm thick) When duct-type or cassette-type unit is to be
installed, it shall be covered with thicker insulating material
(Polyethylene form, 10 mm thick)
1 ea.
1 ea.
1
F-GAS label
8
Installation Manual
Flare tool for R32
4 mm hexagonal wrench
RAS-3M26U2AVG-E
–10 to 46 °C
–10 to 46 °C
–15 to 24 °C
890 mm
900 mm
320 mm
72 kg
1.92 kg
16.4 A
16.1 A
2
2
or more
3 m
25 m
70 m
15 m
40 m
20 g/m (41 m-70 m)
All combinations that do not exceed the "Total"
number can be installed.
More than 2 indoor units must be connected to
an outdoor unit.
When 2 indoor units are connected to an
outdoor unit, note that some combinations of
indoor units are not compatible. For the further
details, refer to the catalogue.
*2 Need the reducer (12.7 to 9.52 mm).
*3 Need the expander (9.52 to 12.7 mm).
• Locally procured.
Drain nipple
1
1