Programmable controller

Advertisement

3) Connecting a cable
• When ferrules with insulation sleeve are used
Insert a wire with the ferrule with insulation sleeve into the wire insertion
opening and push the wire.
• When stranded wires and solid wires are used
Push the open/close button of the terminal block with a flathead
screwdriver. While pushing the open/close button, insert the wire into the
insertion opening until the wire reaches the back, and then release the
open/close button.
Then, pull the wire lightly and check that it is clamped securely.
<Reference>
Manufacturer
Model
PHOENIX CONTACT GmbH & Co.
SZS 0.4×2.5 VDE
KG
4) Disconnecting a cable
Push the open/close button of the wire to be disconnected with a flathead
screwdriver. Pull out the wire with the open/close button pushed.
3.2 Example of Input/output Wiring
24 V DC
FX5-4LC
Power supply
Grounding
(Grounding resistance:
Load
OUT1
Output
100 Ω or less)
COM1
*1
Compensating lead wire
ch
TC+
Thermocouple
TC-
Shielded wire
ch
A
Resistance thermometer
B
Pt100 or Pt1000
(3-wire type)
b
Shielded wire
ch
A
Resistance thermometer
B
Pt1000
Shielded wire
*3
B
(2-wire type)
b
ch
VL+
Micro voltage input
VL-
Shielded wire
AC Power supply
ch
CT
Current sensor (CT)
CT
Controlled
Shielded wire
object
ch
: represents the channel number.
*1 When using a thermocouple, use specified compensating lead wires.
*2 When you use a resistance thermometer, the resistance of the lead wire is
low, use a wire without a resistance difference between the lead wire.
*3 Make sure to short-circuit the [B] and [b] terminals when a 2-wire resistance
thermometer is input.
3.2.1
Power Connector
For further information on the power supply wiring and power cable, refer to the
following manual.
→ MELSEC iQ-F FX5 User's Manual (Temperature Control)
(Green)
( Black )
( Red )
3.3 Grounding
Ground the PLC as stated below.
• Perform class D grounding. (Grounding resistance: 100 Ω or less)
• Ground the PLC independently if possible.
If the PLC cannot be grounded independently, perform the "Shared grounding"
shown below.
For details, refer to the following manual.
→ MELSEC iQ-F FX5U User's Manual (Hardware)
→ MELSEC iQ-F FX5UC User's Manual (Hardware)
Other
Other
Other
PLC
PLC
PLC
equipment
equipment
equipment
Independent grounding
Shared grounding
Common grounding
(Best condition)
(Good condition)
(Not allowed)
• Bring the grounding point close to the PLC as much as possible so that the
ground cable can be shortened.
4. Specification
DESIGN
PRECAUTIONS
• Make sure to set up the following safety circuits outside the PLC to ensure safe
system operation even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
- Most importantly, set up the following: an emergency stop circuit, a protection
circuit, an interlock circuit for opposite movements (such as normal vs. reverse
rotation), and an interlock circuit (to prevent damage to the equipment at the
upper and lower positioning limits).
- Note that when the CPU module detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error that
cannot be detected by the CPU module occurs in an input/output control block,
output control may be disabled.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such a case.
- Note that when an error occurs in a relay, transistor or triac of an output circuit,
the output might stay on or off.
For output signals that may lead to serious accidents, external circuits and
mechanisms should be designed to ensure safe machinery operation in such a case.
DESIGN
PRECAUTIONS
• Simultaneously turn on and off the power supplies of the CPU module and
extension modules.
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
*2
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
*2
environmentally safe recycling and disposal of your device.
TRANSPORTATION
PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product. After transportation, verify
operation of the product and check for damage of the mounting part, etc.
4.1 Applicable CPU Module
Model name
Applicability
FX5U CPU module
Ver. 1.050 or later
*1
Ver. 1.050 or later
FX5UC CPU module
*1 FX5-CNV-IFC or FX5-C1PS-5V is necessary to connect FX5-4LC to the FX5UC
CPU module.
4.2 General Specifications
The items other than the following are equivalent to those of the CPU module.
For the general specification, refer to the following manual.
→ MELSEC iQ-F FX5U User's Manual (Hardware)
→ MELSEC iQ-F FX5UC User's Manual (Hardware)
Items
Specifications
Dielectric withstand
500 V AC for 1 minute
voltage
I n s u l a t i o n
10 MΩ or higher by 500 V DC
resistance
insulation resistance tester
4.3 Power Supply Specifications
Items
Power supply voltage
24 V DC +20%, -15%
E x t e r n a l
O p e r a t i o n
Allowable instantaneous
p o w e r
instantaneous power failure is shorter than
power failure time
supply
5 ms.
Current consumption
25 mA
I n t e r n a l
Power supply voltage
5 V DC
p o w e r
Current consumption
140 mA
supply
4.4 Performance Specifications
Items
Two-position control, PID control,
Control method
Heating/cooling PID control, Cascade control
Control operation period
250 ms/4ch
Measured temperature
Refer to section 4.7
range
Heater disconnection
Alarm is detected (Variable within range from 0.0 to 100.0
detection
A by GX Works3.)
0: Not used, 1: Monitor, 2: Monitor+Alarm,
Operation mode
3: Monitor+Alarm+Control (Selected by GX Works3)
• The photocoupler is used to insulate the analog input
area and transistor output area from the PLC.
• The DC/DC converter is used to insulate the power
Insulation method
supply from the analog input area and transistor
output area.
• Channels are insulated from each other.
Number of occupied I/O
8 points
points
4.5 Input Specifications
Items
Number of input points
4 points
Thermocouple
*1
R e s i s t a n c e
Input type
thermometer
Micro voltage input
Refer to MELSEC iQ-F FX5 User's Manual (Temperature
*2
Measurement precision
Control)
When ambient
temperature is
0 to 55°C
Cold contact temperature
compensation error
When ambient
temperature is
-20 to 0°C
0.1°C (0.1°F), 1.0°C (1.0°F), 0.5 μV or 5.0 μV
Resolution
Varies depending on input range of used sensors.
Sampling period
250 ms/4ch
Effect of external
resistance (When
Approx. 0.125 μV/Ω
thermocouple is used)
Effect of input lead wire
3-wire type
resistance
(When resistance
2-wire type
thermometer is used)
Input impedance
1 MΩ or more
Approx. 0.20 mA
Sensor current
(When resistance thermometer is used)
Operation when input is
disconnected/
Upscale/Downscale
Operation when input is
(When resistance thermometer is used)
Between all terminals and
short-circuited
ground terminal
*1 A different input can be selected for each channel.
*2 To stabilize the measurement precision, warm-up (supply power) the system for
30 minutes or more after power-on.
Specifications
4.6 Current Sensor (CT) Input Specifications
Items
c o n t i n u e s
w h e n
t h e
Number of input points
Current sensor
Allowable input current
Specifications
Heater current measured
value
Measurement precision
Sampling period
4.7 Measured Temperature Range
Input type
K
J
T
S
R
E
B
Specifications
N
PLII
K, J, R, S, E, T, B, N JIS C 1602-1995,
PLII, W5Re/W26Re, U, L
W5Re/W26Re
3-wire type Pt100 JIS C 1604-1997,
U
3-wire type JPt100 JIS C 1604-1981
2-wire type/3-wire type
L
Pt1000 JIS C 1604-2013
Micro voltage input
Pt100 (3-wire type)
JPt100 (3-wire type)
Pt1000 (2-wire type/3-wire type)
Within ±1.0°C
However, within ± 2.0°C while input
4.8 Output Specifications
value is -150 to -100°C / within ± 3.0°C
while input value is -200 to -150°C
Within ±1.8°C
Number of output points
However, within ± 3.6°C while input
value is -150 to -100°C / within ± 5.4°C
Output method
while input value is -200 to -150°C
Rated load voltage
Maximum load voltage
Maximum load current
Leak current in OFF status
ON voltage
Control output cycle
Approx. 0.03%/Ω of full scale.
10 Ω or less per 1-wire
Approx. 0.04%/Ω of full scale.
This manual confers no industrial property rights or any rights of any other kind,
7.5 Ω or less per 1-wire
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
Specifications
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
4 points
a device or system used in purposes related to human life.
When using this product in the United States or
Before using the product for special purposes such as nuclear power, electric
Canada, use current sensors with UL/cUL Listed
power, aerospace, medicine or passenger movement vehicles, consult with
and/or CSA certified such as XOBA and XOBA7.
Mitsubishi Electric.
When using current sensors in countries other
This product has been manufactured under strict quality control. However
than the above, we recommend the following.
when installing the product where major accidents or losses could occur if the
CTL-12-S36-8, CTL-12-S36-10, CTL-12-S56-10,
product fails, install appropriate backup or failsafe functions in the system.
CTL-12L-8, CTL-6-P, CTL-6-P-H, CTL-6-S-H
(manufactured by U.R.D. Co., Ltd.)
0 to 182.2 mArms
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Items
Specifications
When CTL-12-S36-8 is used: 0.0 to 100.0 A
When CTL-12-S36-10 is used: 0.0 to 100.0 A
When CTL-12-S56-10 is used: 0.0 to 100.0 A
When CTL-12L-8 is used: 0.0 to 100.0 A
When CTL-6-P is used: 0.0 to 30.0 A
When CTL-6-P-H is used: 0.0 to 30.0 A
When CTL-6-S-H is used: 0.0 to 30.0 A
Larger one between ±5% of input value and ±2
A (Excluding precision of current sensor)
0.5 sec.
Measurement precision
-200 to +1300°C (-100 to +2400°F)
-200 to +1200°C (-100 to +2100°F)
-200 to +400°C (-300 to +700°F)
0 to 1700°C (0 to 3200°F)
0 to 1700°C (0 to 3200°F)
-200 to +1000°C (0 to 1800°F)
0 to 1800°C (0 to 3000°F)
0 to 1300°C (0 to 2300°F)
0 to 1200°C (0 to 2300°F)
0 to 2300°C (0 to 3000°F)
-200 to +600°C (-300 to +700°F)
0 to 900°C (0 to 1600°F)
DC0 to 10 mV, DC0 to 100 mV
-200 to +600°C (-300 to +1100°F)
-200 to +500°C (-300 to +900°F)
-200.0 to +650.0°C (-328 to +1184°F)
Items
Specifications
4 points
NPN open collector transistor output
5 to 24 V DC
30 V DC or less
100 mA
0.1 mA or less
1.5 V (When maximum load current)
0.5 to 100.0 sec.
For safe use

Advertisement