Installation Instructions; Warning To The User; The Room - Camargue 134 10 15 Technical Manual

En 13240, output: 10 kw
Table of Contents

Advertisement

Camargue - ref. 134 10 15

2. Installation instructions

2.1. Warning to the user

All the local and national regulations, and in
particular those relating to national and European
standards, must be observed when installing the
appliance.
An incorrectly installed heating appliance can
cause serious accidents (chimney fires, burning of
plastic insulation materials, in partition walls, etc.).
The insulation of both the appliance and the
exhaust gas pipe has to be reinforced and done
a c c o r d i n g t o t h e S t a n d a r d s a n d t h e B u i l d i n g
Regulations for safety reasons.
Failure to respect the mounting instructions leads to
engage the responsibility of the one doing the
installation.
The manufacturer's responsibility shall be limited to the
supply of the equipment.

2.2. The room

Ventilation :
For satisfactory operation with a natural draught, check
that sufficient air for combustion is available in the
room.
Position of the unit :
For new chimney installations, select a central position
within the building, to provide a good heat distribution
around the building.
The heat distribution towards the other rooms will be
made through the communicating doors. These rooms
 # 
 # 
4
must be in negative pressure or must include ventilation
gratings.
Floor and walls :
Make sure that the floor can support the weight of the
appliance, its surroundings and the hood. In the
contrary the floor needs to be reinforced with a concrete
screed to distribute this load.
Make sure there are not combustible or covered with
combustible material.
O t h e r w i s e i t m u s t n e c e s s a r y t o i n s t a l l a
non-combustible protection.
There must be a clearance of at least 150 mm at each
side of the appliance and at the back of the appliance
from a non-combustible wall.
This distance must be extended to a minimum
clearance of 400 mm from any combustible materials.
This measurement may be reduced to a minimum gap
of 50 mm when the non-combustible wall is at least
200 mm thick.
There should ideally be a minimum gap of 400 mm at
the right hand side of the stove, this will ensure the best
possible access to the loading door.
When using a single wall flue pipe, there must be a
clearance (A) of at least three times its diameter (B)
from any combustible materials.
If the appliance has to be located in an opening, this
distance must be extended to a minimum clearance (A)
of 450 mm from the pipe or the stove body to any
combustible materials.
"  
Figure 2 - Minimum clearances
*
)
)
+
!  
Installation instructions
 # 
Technical manual "1141"

Advertisement

Table of Contents
loading

Table of Contents