C3-100 Installation Instructions and Connection Guide
Vision:1. 0 .1
1.
Cautions
Please note the following cautions.Mis-operation may lead to personal injury or equipment failure:
1) Do not energize the system before installation is complete; never carry out installation activities when
the system is energized.
2) All peripheral devices must be grounded.
3) It is preferred that all wires run through PVC or galvanized pipes.
4) It is strongly recommended that the length of exposed part of any connection cable should not be longer
than 4 mm.
Professional clamping tools may be used to avoid unintentional contact of exposed wires to
avoid
short-circuit or communication failure.
5) It is recommended that card readers and buttons should be installed at height of 1.4m-1.5m above ground.
6) It is recommended to use the power supply in case for control panel, and external power supply for each
lock.
Description of normal working state:
Connect the system to the power supply.If the system works properly,the POWER indicator(red) is lit
constantly and the RUN indicator(green) flashes.
2.
Components
Key hole
Heat
dissipation
hole
Thread hole
Appearance of case
3.
Get through the thread hole
Thread hole
1
Get through the thread hole
Date:Oct. 2010
Backup battery
Power supply
Control panel
2
Fixed case
4.
LED indicators, Wires, Auxiliary Input and Output
Notes:
1)Meaning of LED indicators:
LINK indicator(green): always(green) indicates TCP/IP
communication is proper;
ACT indicator(yellow):its flashing indicates data is in transmitting
through TCP/IP communication.
TX indicator(yellow):its flashing indicates it is sending data through
RS485 communication.
RX indicator(green):its flashing indicates it is receiving data through
RS485 communication.
Auxiliary output indicator(green):always(green) indicates it is in use.
Lock indicator(green):always(green) indicates lock is open.
POWER indicator(red): always(red) indicates control panel is power
on.
RUN indicator(green):its flashing indicates the system works normally.
CARD indicator(yellow):its flashing indicates card is punched on reader.
LINK
Ethernet interface
ACT
Advanced Access Control
Dip switch
485+
485-
RS485 interface
GND
TX
RX
{
NO
D
COM
Auxiliary output1
NC
{
SEN
GND
C
NO
Door1
COM
NC
A
V+
Power of lock
V-
A
+12V
Power of control panel
GND
2)Recommended use of wires:
A Use 2-conducotor power cord
B Use 6-conductor wire between wiegand reader and control panal
(RVVP 6*0.5mm) (To choose the proper cord according to the
interface you connect, such as 6,8,10 cord.)
C Use 4-conducotor lock power cord (RVV 4*0.75mm)
D Use 2-conducotor switch power cord(RVV 2*0.5mm)
3)The auxiliary input may be connnected to infrared body detectors,
alam switches,etc.
4)The auxiliary output may be connected to door bells,alarms,etc.
SD card
IN
GND
BEEP
GLED
WD1
WD0
GND
+12V
BEEP
GLED
WD1
WD0
GND
POWER
+12V
RUN
CARD
D
1# Door Button
B
1# Door
wiegand reader
B
1# Door
wiegand reader