Online UPS Specialist Pty Ltd PP1KL User Manual page 17

Table of Contents

Advertisement

2. Position and way of connection, refer to figure 15.
3. Output power cable is designed according to load current, do not use
over-thin cable. Please refer to Table 2
Model
Online UPS PP1KL
Online UPS PP2KL
Online UPS PP3KL
Online UPS PP4KL
Online UPS PP5KL
Online UPS PP6KL
Online UPS PP8KL
Online UPS PP10KL
Online UPS PP12KL
Online UPS PP15KL
4. Avoid short-circuit and overload.
5. The comparison between output current rating and output cable size is
listed in Table 2.
6. The ground to this unit only acts as reference point, if the ground isn't
good, that may cause disturbance and false datum management, and
affect UPS and computer, please ask professional personnel for handling
immediately.
7. User offers a good grounding system.
8. Try to make the ground close to connecting point of grounding club or
Max. output current
4A
8A
12A
16A
20A
24A
32A
40A
48A
60A
Table 2
- 14 -
Output cable
Terminal specification
12AWG
10AWG
10AWG
10AWG
10AWG
10AWG
8AWG
8AWG
8AWG
5AWG
5.5~6
5.5~6
5.5~6
5.5~6
5.5~6
5.5~6
8.5~9
8.5~9
8.5~9
16~9